Manual

10 Technical data
INPUTS
PROCESS VALUE INPUT INP1
Resolution: > 14 bits
Decimal point: 0 to 3 digits behind the decimal
point
Dig. input filter: adjustable 0,000...9999 s
Scanning cycle: 100 ms
Measured value
correction:
2-point or offset correction
Thermocouples
r Table 1 (page 76 )
Internal and external temperature compensation
Input resistance:
1M
Effect of source resistance: 1 µV/
Internal temperature compensation
Maximal additional error: ± 0,5 K
Sensor break monitoring
Sensor current:
1
µ
A
Configurable output action
Thermocouple to specification
Measuring range -25...75mV in conjunction with
the linearization can be used for connecting
thermocouples which are not included in Table 1.
Resistance thermometer
r Table 2 (page 76 )
Connection: 3-wire
Lead resistance: max. 30 Ohm
Input circuit monitor: break and short circuit
Special measuring range
BlueControl (engineering tool) can be used to
match the input to sensor KTY 11-6 (character
-
istic is stored in the controller).
Physical measuring range: 0...4500 Ohm
Linearization segments 16
Current and voltage signals
r Table 3 (page 76 )
Span start, end of span: anywhere within measuring
range
Scaling: selectable -1999...9999
Linearization: 16 segments, adaptable with
BlueControl
Decimal point: adjustable
Input circuit monitor: 12,5% below span start (2mA,
1V)
SUPPLEMENTARY INPUT INP2
Resolution: > 14 bits
Scanning cycle: 100 ms
Heating current measurement
via current transformer ( Accessory equipment)
Measuring range: 0...50mA AC
Scaling: adjustable -1999...0,000...9999 A
Current measuring range
Technical data as for INP1
Potentiometer
r Table 2 (page 76 )
Connection: 2-wire
Lead resistance: max. 30 Ohm
Input circuit monitor: Break
SUPPLEMENTARY INPUT INP3 (OPTION)
Resolution: > 14 bits
Scanning cycle: 100 ms
Technical data as for INP1 except 10V range.
CONTROL INPUTS DI1, DI2
Configurable as switch or push-button!
Connection of a potential-free contact suitable
for switching “dry” circuits.
Switched voltage: 5 V
Current: 100
µ
A
Technical data
72 KS 90-1 / KS 92-1