9499-040-93811 / 59537-1 Page 51 of 88 Pro-16
4.4.6 KS 20-1 with measured value output
Example: KS20-10H-LR000-000
ConF/Out.3:O.tYP
= 1
Out.3 0...20mA continuous
= 2
Out.3
4...20mA continuous
= 3
Out.3
0...10V continuous
= 4
Out.3
2...10V continuous
Out.0 = -1999...9999
Scaling Out.3 for 0/4mA e.g. 0/2V
Out.1 = -1999...9999
Scaling Out.3 for 20mA e.g. 10V
O.Src = 3
Signal source for Out.3 is the process value