Instruction Manual

Configuration level
9499-040-93811 / 59537-1 Page 50 of 88 Pro-16
4.4.5 - Y - Off controller / 2-point controller with pre-contact
ConF/Cntr: SP.Fn
= 0
set-point / cascade controller
C.Fnc
= 2
D -Y-Off controller
C.Act
= 0
inverse action (e.g. heating applications)
ConF/Out.1:
O.Act
= 0
action Out.1 direct
Y.1
= 1
control output Y1 active
Y.2
= 0
control output Y2 not active
ConF/Out.2:
O.Act
= 0
action Out.2 direct
Y.1
= 0
control output Y1 not active
Y.2
= 1
control output Y2 active
PArA/Cntr: Pb1
= 1...9999
proportional band 1 (heating) in units of phys.
quantity (e.g. °C)
ti1
= 0,1...9999
integral time 1 (heating) in sec.
td1
= 0,1...9999
derivative time 1 (heating) in sec.
t1
= 0,4...9999
min. cycle time 1 (heating)
SH
= 0...9999
switching difference
d.SP
= -1999...9999
trigg. point separation suppl. cont.
PArA/SEtP: SP.LO
= -1999...9999
D / Y / Off in units of phys. quantity
SP.Hi
= -1999...9999
set-point limit low for Weff