9499-040-93811 / 59537-1 Page 47 of 88 Pro-16
4.4.2 2-point and continuous controller (inverse)
C
on
F
/
C
n
t
r
SP
.
F
n
= 0 set-point / cascade controller
C
.
F
nc
= 1 2-point and continuous controller (PID)
C
.
A
c
t
= 0 inverse action (e.g. heating applications)
C
on
F
/
O
u
t
.
1
:
O
.
A
c
t
= 0 action Out.1 direct
Y
.
1
= 1 control output Y1 active
C
on
F
/
O
u
t
.
3
:
O
.
tYP
= 1 / 2 Out.3 Type ( 0/4 … 20mA)
O
u
t
.
0
= -1999...9999 scaling analog output 0/4mA
O
u
t
.
1
= -1999...9999 scaling analog output 20mA
O
.
S
rc
= 1 controller output y1 (continuous)
PArA/Cntr: Pb1 = 1...9999 proportional band 1 (heating) in units of phys. quantity
(e.g. °C)
ti1
= 0,1...9999 integral time 1 (heating) in sec.
td1
= 0,1...9999 derivative time 1 (heating) in sec.
t1
= 0,4...9999 min. cycle time 1 (heating)
PA
r
A
/
SEtP
:
SP
.
LO
= -1999...999 set-point limit low for Weff
SP
.
Hi
= -1999...9999 set-point limit high for Weff
g
For direct controller action, the controller action must be changed
( ConF / Cntr / C.Act = 1 )