Instruction Manual
Configuration
level
9499-040-93811 / 59537-1 Page 33 of 88 Pro-16
0 not active
1 active
Out.0
-1999...9999
Scaling of the analog output for 0% (0/4mA or 0/2V, only
visible when
O
.
TYP
=1..5)
0
Out.1
-1999...9999
Scaling of the analog output for 100% (20mA or 10V, only
visible when
O
.
TYP
=1..5)
100
O.Src
Signal source of the analog output OUT3 (only visible when
O
.
TYP
=1..5)
1
0 not used
1 controller output y1 (continuous)
2 controller output y2 (continuous)
3 process value
4 effective set-point Weff
5 control deviation xw (process value - set-point)
6 No function
fOut Forcing OUT1 (only visible with BlueControl!) 0
0 No forcing
1 Forcing via serial interface
Out.3
Configuration parameters Out.2 as Out.1 except for: Default Y.1 = 0, Y.2 = 1
Out.5
Configuration parameters Out.5 as Out.1 except for default values:
All values are 0!
Out.2 / 4 / 6
Name Value range Description Default
O.Act
Method of operation of output
1
0 direct / normally open
1 inverse / normally closed
Y.1
Y.2
Controller output Y1/Y2 0
0 not active
1 active
Lim.1
Lim.2
Lim.3
Limit 1/2/3 signal 1
0 not active
1 active
LP.AL
Interruption alarm signal (LOOP) 0
0 not active
1 active
HC.AL
Heating current alarm signal 0