Instruction Manual

Configuration
level
9499-040-93811 / 59537-1 Page 31 of 88 Pro-16
Lim
Name Value range Description Default
Fnc.1
Fnc.2
Fnc.3
Function of limit 1/2/3 1
0 switched off
1 measured value monitoring
2 Measured value monitoring + alarm status storage. A stored
limit value can be reset via error list, è-key, or a digital
input ( ->
LOGI
/
E
rr.r)
Src.1
Src.2
Src.3
Source of Limit 1/2/3 1
0 process value
1 control deviation xw (process value - set-point)
2 control deviation xw (with suppression after start-up and
set-point change)
6 effective setpoint Weff
7 correcting variable y (controller output)
8 control variable deviation xw (actual value - internal
setpoint) = deviation alarm to internal setpoint
11 Control deviation Xw (=relative alarm) with suppression
after start-up or set-point change without time limit.
HC.AL
Alarm heat current function (INP2) 0
0 switched off
1 Overload short circuit monitoring
2 Break and short circuit monitoring
LP.AL
Monitoring of control loop interruption for heating 0
0 switched off / inactive
1
LOOP alarm active. A loop alarm is output, unless the process value
reacts accordingly after elapse of 2 xti1 with Y=100%.
With ti1=0 , the LOOP alarm is inactive!
Hour OFF..999999 Operating hours (only visible with BlueControl
®
!) OFF
Swit OFF..999999 Output switching cycles (only visible with BlueControl
®
!) OFF
Out.1
Name Value range
Description Default
O.tYP
Signal type selection OUT1 0
0 relay / logic (only visible with current/logic voltage)
1 0 ... 20 mA continuous (only visible with current/logic/voltage)
2 4 ... 20 mA continuous (only visible with current/logic/voltage)
3 0...10 V continuous (only visible with current/logic/voltage)