Instruction Manual

Configuration level
9499-040-93811 / 59537-1 Page 30 of 88 Pro-16
23 special 0...4500 Ohm (pre-defined as KTY11-6)
30
0...20mA / 4...20mA Scaling is required (see chp.  page 57)
40 0...10V / 2...10V Scaling is required (see chp.  page 57)
S.Lin
Linearization (only at S.tYP = 23 (KTY 11-6), 30 (0..20mA)
and 40 (0..10V) adjustable) (see page 74)
0
0 Without linearization
1 Linearization to specification. Creation of linearization table
with BlueControl (engineering tool) possible. The
characteristic for KTY 11-6 temperature sensors is preset.
Corr Measured value correction / scaling 0
0 Without scaling
1 Offset correction (at CAL level) (see page 58)
2 2-point correction (at CAL level 58)
3 Scaling (at PArA level) (see page 57)
fAI1 Forcing INP1 (only visible with BlueControl
®
!) 0
0 No forcing
1 Forcing via serial interface
InP.2
Name Value range Description Default
I.Fnc
Function selection of INP2 1
0 no function (subsequent input data are skipped)
1 heating current input
2 external set-point (
S
P.E)
5
default correcting variable Y.E (switchover ->
L
OGI
/
Y
.E
)
S.tYP
Sensor type selection 31
30
0...20mA / 4...20mA Scaling is required (see chp.  page 57)
31 0...50mA AC Scaling is required. (see chp.  page 57)
fAI2 Forcing INP2 (only visible with BlueControl
®
!) 0
0 No forcing
1 Forcing via serial interface