Instruction Manual

Configuration
level
9499-040-93811 / 59537-1 Page 29 of 88 Pro-16
tunE Auto-tuning at start-up 0
0 At start-up with step function
1 At start-up with impulse function. Setting for fast controlled
systems (e.g. hot runner control)
2 Always step attempt during start-up
Strt Start of auto-tuning 0
0 no automatic start (manual start via front interface)
1 Manual or automatic start of auto-tuning at power on or when
oscillating is detected
Adt0 Optimization of T1, T2 (only visible with BlueControl!) 0
0 Automatic optimization
1 No optimization
Prog
Name Value range Description Default
t.bAS
Time base 0
0 hours:minutes
1 minutes:seconds
InP.1
Name Value range Description Default
S.tYP
Sensor type selection 1
0 thermocouple type L (-100...900°C) , Fe-CuNi DIN
1 thermocouple type J (-100...1200°C) , Fe-CuNi
2 thermocouple type K (-100...1350°C), NiCr-Ni
3 thermocouple type N (-100...1300°C), Nicrosil-Nisil
4 thermocouple type S (0...1760°C), PtRh-Pt10%
5 thermocouple type R (0...1760°C), PtRh-Pt13%
6 thermocouple type T (-200…400°C), Cu-NiCu
7 thermocouple type C (0...2315°C), W5%Re-W26%Re
8 thermocouple type D (0...2315°C), W3%Re-W25%Re
9 thermocouple type E (-100...1000°C), NiCr-CuNi
10 thermocouple type B (0/100...1820°C), PtRh-Pt6%
18 special thermocouple
20 Pt100 (-200.0 ... 100,0 °C)
( -200,0 ... 150,0°C with reduced lead resistance: measuring
resistance + lead resistance 160[)
21 Pt100 (-200.0 ... 850.0 °C)
22 Pt1000 (-200.0 ... 850.0 °C)