User Manual
Operating Conditions
Ambient Temperature
(Operating):
0 °C to 55 °C
Ambient Temperature
(Storage):
–20 °C to 80°C
Relative Humidity: 20% - 95% non-condensing
Supply Voltage: 90 - 264V AC 50/60Hz (standard)
20 - 50V AC 50/60Hz or 22 - 65V DC
(option)
Source Resistance: 1000 Ω maximum (thermocouple)
Lead Resistance: 50Ω per lead maximum balanced (Pt100)
Performance Under Operating Conditions
Temperature Stability:
0.01% of span/°C change in ambient
temperature.
Cold Junction
Compensation
(thermocouple Only):
Better than ±1°C.
Supply Voltage Influence: Negligible.
Relative Humidity
Influence:
Negligible
Sensor Resistance
Influence:
Thermocouple 100Ω : <0.1% of span error
Thermocouple 1000Ω : <0.5% of span error
RTD Pt100 50 Ω/lead: <0.5% of span error
A.9 ENVIRONMENTAL
Operating Conditions: See Subsection A.8 - PERFORMANCE.
Approvals: CE, UL, ULC
EMI Susceptibility: Certified to EN50082-1:1992 and
EN50082-2:1995.
NOTE: For line-conducted disturbances
induced by RF fields (10V 80% AM 1kHz),
the
1
16
-DIN controller is self-recoverable in
the frequency bands 17 - 47MHz and 68 -
80MHz.
A-11 S054-A
59125