User Manual

3.3.3 Setpoint Parameters
3.3.4 Alarm Parameters
For descriptions of the operation of the different alarm types, see Figure 2-3.
O054-3 3-7
59125
Parameter Identifier Description
Setpoint
value
S May be read (Type 2 message) or modified (Type
3/Type 4 message sequence). Limited by Setpoint High
Limit and Setpoint Low Limit (see below).
Setpoint
Ramp Rate
^ May be read (Type 2 message) or modified (Type
3/Type 4 message sequence). May be set in the range
1 - 9999 increments/hour or OFF ({DATA} =0000).
Decimal point position is as for input range.
Setpoint High
Limit
A May be read (Type 2 message) or modified (Type
3/Type 4 message sequence). Defines maximum value
for setpoint (in the range setpoint - Input Range
Maximum). Decimal point position is as for input
range.
Setpoint Low
Limit
T May be read (Type 2 message) or modified (Type
3/Type 4 message sequence). Defines minimum value
for setpoint (in the range Input Range Minimum -
setpoint). Decimal point position is as for input range.
Parameter Identifier Description
Alarm 1 value C May be read/modified by a Type 2 message or a
Type 3/Type 4 message sequence. Decimal point
position is as for input range.
Alarm 2 value E May be read/modified by a Type 2 message or a
Type 3/Type 4 message sequence. Decimal point
position is as for input range.