Manual

Operating Conditions
Ambient Temperature:
0°C to 55 °C
Relative Humidity: 20% - 95% non-condensing
Performance Under Operating Conditions
Temperature Stability:
0.005% of span/°C change in ambient
temperature.
A.10 ENVIRONMENTAL
EMI Susceptibility: Complies with EN50082-1:1992,
EN50082-1:1995.
NOTES:
1. For RF electromagnetic fields (10V/m 80% AM 1kHz), the reading
accuracy may be impaired by up to 0.3% in the frequency band
87 to 109MHz.
2. For line-conducted disturbances induced by RF fields (10V 80%
AM 1kHz), the product is self-recoverable in the frequency band
0.15 - 0.73MHz.
EMI Emmissions: Complies with EN50081-1:1992,
EN50081-2:1993.
Safety: Complies with EN61010-1.1993.
Supply Voltage: 90 - 264V, 50/60Hz (standard)
20 - 50V AC/DC (option)
Power Consumption: 4watts approximately
Front Panel Sealing: To IP66 (Nema 4)
A.11 PHYSICAL
Dimensions: Height - 48mm
Width - 96mm
Depth - 100mm
Mounting: Panel-mount; press-fit fixing strap supplied.
Panel cut-out - 45mm x 92mm
Terminals: Screw type; combination head.
Weight: 0.21kg maximum.
PM091-A Volume II A-4
59136