Manual
OM091-3 Volume I 3-4
59136
Identifier Hex. Parameter Adjustment Range
: 3A Process Variable
Read Only (−19999 to 9999)
; 3B Total value
Read Only (−19999 to 9999)
< 3C Maximum Process Variable
Read Only (−19999 to 9999)
= 3D Minimum Process Variable
Read Only (−19999 to 9999)
> 3E Elapsed Alarm 1 Time Read Only (0 to 60000)
@ 40 Reset Max. PV Write resets; Read always 0
A 41 Reset Min. PV Write resets; Read always 0
B 42 Reset Elapsed Alarm 1 Time Write resets; Read always 0
C 43 Reset Total value Write resets; Read always 0
D 44 Reset Latched Alarm 1 Write resets; Read always 0
E 45 Alarm 1 value Range Max. To Range Min.
F 46 Alarm 2 value Range Max. To Range Min.
G 47 Scaling Point 1 0 to 100.00
H 48 Display Point 1
−19999 to 9999
I 49 Scaling Point 2 Scaling Point 1 to 100.00
J 4A Display Point 2
−19999 to 9999
⇓ Up to a total of 10 Scaling Points and 10 Display Points are available.
⇓ Scaling Point 1 ≤ Scaling Point 2 ≤ Scaling Point 3 etc.
⇓ Any Scaling Point set to 100.00% is automatically the last available.
Z 5A Scaling Point 10 Scaling Point 9 to 100.00
[ 5B Display Point 10
−19999 to 9999
\ 5C Decimal Point Position 0 (00000) to 4 (0.0000)
] 5D Re-transmitted Scale Min.
−19999 to Re-trans. Scale Max.
^ 5E Re-transmitted Scale Max. Re-trans. Scale Min. To 99999
_ 5F Process Variable Offset 0 to Range Span
‘ 60 Input Filter 0 to 1000 (0.0 to 100.0s)
a 61 Colour 0 to 3 (0 = Red, 1 = Green,
2 = Green/Red, 3 = Red/Green)
b 62 Alarm Lock 0 (lock enabled), 1 (lock disabled)
c 63 Help level 0 (Help enabled), 1 (Help disabled)
Table 3 -1 Parameter Identifiers and Adjustment Ranges