Owner's manual
A.11 PERFORMANCE
Reference Conditions
Generally as EN60546-1.
Ambient Temperature:
20°C ±2°C
Relative Humidity: 60 - 70%
Supply Voltage: 90 - 264V AC 50Hz 1%
Source Resistance: <10Ω for thermocouple input
Lead Resistance: <0.1Ω/lead balanced (Pt100)
Performance Under Reference Conditions
Common Mode Rejection: >120dB at 50/60Hz giving negligible effect
at up to 264V 50/60Hz.
Series Mode Rejection: >500% of span (at 50/60Hz) causes
negligible effect.
Thermocouple Inputs
Measurement Accuracy:
±0.25% of span ±1LSD.
Linearisation Accuracy:
Better than ±0.2 °C any point, any 0.1°C
range (± 0.05°C typical). Better than ±0.5 °C
any point, any 1 °C range.
Cold Junction
Compensation:
Better than ±0.7 °C.
RTD Inputs
Measurement Accuracy:
±0.25% of span ±1LSD
Linearisation Accuracy:
Better than ±0.2 °C any point, any 0.1°C
range (± 0.05°C typical). Better than ±0.5 °C
any point, any 1 °C range.
DC Output - Accuracy
Output 3 (Recorder
Output):
±0.25% (mA @ 250 Ω, V @ 2kΩ ); Degrades
linearly to ± 0.5% for increasing burden (to
specification limits).
S075-A A-10
PM-0075