Owner's manual

A.4 OUTPUT 1
General
Types Available: Relay, SSR Drive/TTL and Solid State.
Relay
Contact Type: Single pole double throw (SPDT).
Rating: 2A resistive at 120/240V AC.
Lifetime: >500,000 operations at rated
voltage/current.
Isolation: Inherent.
SSR Drive/TTL
Drive Capability: SSR >10V DC into 500 minimum.
Isolation: Not isolated from input or other SSR outputs.
Solid State
Operating Voltage Range: 20 - 280Vrms (47 - 63Hz)
Current Rating:
0.01 - 1A (full cycle rms on-state @ 25°C);
derates linearly above 40 °C to 0.5A @
80 °C.
Max. Non-repetitive Surge
Current (16.6ms):
25A peak
Min. OFF-State
dv
dt
@ Rated
Voltage:
500V/µs
Max. OFF-State leakage @
Rated Voltage:
1mA rms
Max. ON-State Voltage
Drop @ Rated Current:
1.5V peak.
Repetitive Peak OFF-state
Voltage, Vdrm:
600V minimum.
S075-A A -4