User Manual

30
15* Hysteresis for HyCo 0 to 300
3
Control Outputs Width of Hysteresis Band
(See page 66 for definition)
16 Hysteresis for HyAo 0 to 300
3
Alarm Outputs Width of Hysteresis Band
(see page 66 for definition)
17* Remote Setpoint rSP 0 to 2
0
If rSP is set to zero 0=Not Used
then rSPu and rSPL 1=1 to 5 VDC
are not seen 2=0 to 5 VDC
18* Remote Setpoint rSPu -9999 to 9999
1400
Upper Value
19* Remote Setpoint rSPL -9999 to 9999
0
Lower Value
20* Setpoint Upper Limit SPuL -9999 to 9999
1400
21* Setpoint Lower Limit SPLL -9999 to 9999
0
22* Automatic Transfer AtFr 0 to 2
0
0 = No Automatic Transfer
1=Transfers when the process
value goes below the setpoint
2=Transfers when the process
value goes above the setpoint
23 Process Rounding Prnd 0 to 100
0
of Displayed Value 0 = No rounding
24 Display Filter Factor dFF 1 to 20
1
1= no filtering
(number of values averaged)
25 Process Filter Factor PFF Same selection as dFF
1
26 Process Value Output Pout 0=Not selected
0
Retransmission 1=Selected
(If Pout =0 then Pou and
PoL will not be displayed)
27 Process Output Pou -9999 to 9999
2000
Upper Value
28 Process Output PoL -9999 to 9999
0
Lower Value
29 Chart Range Cru -9999 to 9999
200
Upper Value
30 Chart Range CrL -9999 to 9999
0
Lower Value
31* Proportional P1EC 0 to 100%
0
Output 1 Action
on Error Condition
(If out1= 0,1,2 then
P1EC will not be displayed)
32* Proportional P2EC 0 to 100%
0
DISPLAY AVAILABLE FACTORY YOUR
STEP DESCRIPTION CODES SETTINGS SETTING SETTING