TABLE 3-3 PROFILE ENTRY MODE CONFIGURATION PROCEDURE
Depress and release the SCROLL key until PEnt is displayed. Use the DOWN key to enter
the Profile Entry mode. Depress the SCROLL key to scroll through the parameters and their
values. Use the UP and DOWN keys to adjust the values. After adjusting a parameter,
depress the SCROLL key to proceed to the next parameter. After all selections have been
made, to exit the mode, depress the UP key with a parameter in the display (not a setting) to
exit the mode. For assistance in developing the Profile, refer to Appendix F (page 81).
1 Profile Number Pn 1 to 8 **
2 Number of Segments nS 0-6 segments **
Steps 3 - 18 are repeated for each segment
3 Ramp Time rt 0 to 9999 units per Ptb **
4 Setpoint Pen 1 SP1 Setpoint at end of Ramp **
4A Setpoint Pen 2 SP2 Setpoint at end of Ramp **
Note: will appear on lower display if Pen 2 is present
5 *Event Output 1 E1 on or off **
6 *Event Output 2 E2 on or off **
7 *Event Output 3 E3 on or off **
8 *Event Output 4 E4 on or off **
9 *Event Output 5 E5 on or off **
10 *Event Output 6 E6 on or off **
11 Soak Time St 0 to 9999 units per Ptb **
12 *Event Output 1 E1 on or off **
13 *Event Output 2 E2 on or off **
14 *Event Output 3 E3 on or off **
15 *Event Output 4 E4 on or off **
16 *Event Output 5 E5 on or off **
17 *Event Output 6 E6 on or off **
18 Profile Loop Count PLCt 0 to 9999, 0=continuous **
19 Deviation Hold after dhru 0 to 3000 units, **
Ramp Up for P en 1 0=no auto hold
20 Deviation Hold after dhrd 0 to 3000 units, **
Ramp Down for Pen 1 0=no auto hold
21 Deviation Hold after dhru 0 to 3000 units, **
Ramp Down for Pen 2 0=no auto hold **
22 Deviation Hold after dhrd 0 to 3000 units, **
Ramp Down for Pen 2 0=no auto hold **
DISPLAY AVAILABLE FACTORY YOUR