Owner manual

34
53 Pen(s) Profile/ (Control) PPC 1 or 2
1
Profiles/(Profile) 1=Pen 1 profiles & controls
Configuration process.
(only seen on 2 pen instr.) Pen 2 (if present) records
& controls process.
2=Pen 1 profiles & controls
process.
Note: Time base between
both pens are shared.
54 Chart Rotation Time Crt 0.1 to 999.9 hours per
1.0
rotation
55 Pen Action on Power Up PAPu 0=Pen(s) go to the "home"
0
posistion (toward chart
cetner) when powered up
1=Pen(s) remain in last
position prior to power down
56 Chart Operation Coo 0 to 1
0
in Off Mode 0=Chart continues rotating
in the Off mode
1=Chart stops rotating while
in the Off mode
COMMUNICATIONS OPTIONS PARAMETERS
57 Communication CCon 0 to 4
3
Configuration 0=Off
1=Monitor Mode (Read Only)
2=Normal Mode (Read and Write)
3=Total Access with Limit Checking
4=Total Access without Limit Checking
58 Communication Bit CbS 1 to 6
6
Rate Selection 1=300
Will not be seen if 2=600
Con=0 3=1200
4=2400
5=4800
6=9600
59 Communications CAd1 0 to 99
1
Address-Pen 1
Will not be seen if
Con=0
60 Communications CAd2 0 to 99
2
Address-Pen 2
(If provided)
Will not be seen if
Con=0
DISPLAY AVAILABLE FACTORY YOUR
STEP DESCRIPTION CODES SETTINGS SETTING SETTING