24 Display Filter Factor dFF 1 to 20
1
1= no filtering
(number of values averaged)
25 Process Filter Factor PFF Same selection as dFF
1
26 Process Value Output Pout 0=Not selected
0
Retransmission 1=Selected
(If Pout =0 then Pou and
PoL will not be displayed)
27 Process Output Pou -9999 to 9999
2000
Upper Value
28 Process Output PoL -9999 to 9999
0
Lower Value
29 Chart Range Cru -9999 to 9999
200
Upper Value
30 Chart Range CrL -9999 to 9999
0
Lower Value
31 Proportional P1EC 0 to 100%
0
Output 1 Action
on Error Condition
(If out1= 0,1,2 then
P1EC will not be displayed)
32 Proportional P2EC 0 to 100%
0
Output 2 Action
on Error Condition
(If out2 = 0,1,2,7 then
P2EC will not be displayed)
33 Pen Action on PAEC 0 or 1
1
Error Condition 0 = Pen goes to 0 % of chart
1 = Pen goes to 100 % of chart
Pressing the SCROLL key with the PAEC parameter value displayed in the Pen 1 window will
advance the display of a single pen instrument to the unit parameters. Pressing the SCROLL
key with the PAEC parameter displayed in the Pen 1 window of a two pen instrument will
advance the display to be PEns in the Pen 2 window. The Pen 2 Program mode parameter
selections can be made now. Pressing the SCROLL key with the PAEC parameter value
displayed in the Pen 2 window will cause the display to advance to the unit parameters
displayed in the Pen 1 window.
UNIT PARAMETERS
34 Relay A Assignment rLyA 0 to 14
0
1=Assigned to Alarm 1-Pen 1
2=Assigned to Alarm 2-Pen 1
3=Assigned to Alarm 1-Pen 2
4=Assigned to Alarm 2-Pen 2
5=Assigned to Output 1-Pen 1
6=Assigned to Output 2-Pen 1
7=Assigned to Output 1-Pen 2
8=Assigned to Output 2-Pen 2
9=Assigned to Event 1
10=Assigned to Event 2
11=Assigned to Event 3
12=Assigned to Event 4
13=Assigned to Event 5
14=Assigned to Event 6
DISPLAY AVAILABLE FACTORY YOUR
STEP DESCRIPTION CODES SETTINGS SETTING SETTING