Owner manual

31
9 Alarm 1 AL1 0 to 6
0
the Alarm Point 0 = None
is selected in the 1=Process Alarm-Direct
Tune mode 2=Process Alarm-Reverse
3=Deviation Alarm-Direct
4=Deviation Alarm-Reverse
5=Deviation Band Alarm-Open within band
6=Deviation Band Alarm-Closed within band
10 Alarm 2 AL2 Same selections as Alarm 1
0
11 Display Select diSP 1=Process value only
1
2=Process value/setpoint
3=Deviation only
4=Deviation and setpoint
5=Setpoint only
12 Decimal Position dPoS 0 to 3
0
0=None
1=One decimal place
2=Two decimal places
3=Three decimal places
RTD and thermocouple inputs
are limited to either 0 or 1 decimal positions
13 Engineering Units Euu -9999 to 9999
1000
Upper Value (Euu and
EuL will be seen if the pen
input select = 30,31,32,33,34)
14 Engineering Units EuL -9999 to 9999
0
Lower Value
15 Hysteresis for HyCo 0 to 300
3
Control Outputs Width of Hysteresis Band
(See page 70 for definition)
16 Hysteresis for HyAo 0 to 300
3
Alarm Outputs Width of Hysteresis Band
(see page 70 for definition)
17 Remote Setpoint (Pen 2 only) rSP 0 to 2
0
If rSP is set to zero 0=Not Used
then rSPu and rSPL 1=1 to 5 VDC
are not seen 2=0 to 5 VDC
18 Remote Setpoint rSPu -9999 to 9999
1400
Upper Value (Pen 2 only)
19 Remote Setpoint rSPL -9999 to 9999
0
Lower Value (Pen 2 only)
20 Setpoint Upper Limit SPuL -9999 to 9999
1400
21 Setpoint Lower Limit SPLL -9999 to 9999
0
22 Automatic Transfer AtFr 0 to 2
0
0 = No Automatic Transfer
1=Transfers when the process
value goes below the setpoint
2=Transfers when the process
value goes above the setpoint
23 Process Rounding Prnd 0 to 100
0
of Displayed Value 0 = No rounding
DISPLAY AVAILABLE FACTORY YOUR
STEP DESCRIPTION CODES SETTINGS SETTING SETTING