Owner's manual
18
To enter the desired section of the Program mode, press the DOWN arrow key when the desired section is displayed.
Use the keys as defined previously to enter modes and sections, move around, and modify parameter settings. The param-
eters, their definitions, and range of adjustment, are as follows:
PEN 1 AND PEN 2 SECTIONS OF PROGRAM MODE
- PEn1 and PEn2
(Pen 2 will appear only if present in the recorder.)
These parameters apply to each pen, assuming pen 2 is present, and are configured in each respective section.
PARAMETER PARAMETER DEFAULT
CODE DESCRIPTION SETTINGS OR RANGE SETTING
InPS Input Selection 0 - 18 1
0 = J T/C 0 to 760°C
1 = J T/C 0 to 1400°F
2 = K T/C 0 to 1360°C
3 = K T/C 0 to 2500°F
4 = T T/C -200 to 400°C
5 = T T/C -330 to 750°F
6 = R T/C 200 to 1650°C
7 = R T/C 400 to 3000°F
8 = S T/C 200 to 1650°C
9 = S T/C 400 to 3000°F
10 = RTD 100 ohm -140 to 400°C
11 = RTD 100 ohm -200 to 750°F
12 = 0-20mA
13 = 4-20mA
14 = 0-50mV
15 = 10-50mV
16 = 0-25mV
17 = 0-5VDC
18 = 1-5VDC
ICor Input Correction -999 to 999* 0
(calibrates sensor to
recorder)
A1 Alarm Type OFF = none OFF
(will show only if present) Hi = High Alarm
Lo = Low Alarm
HL = High Limit
LL = Low Limit
A2 Alarm Type OFF = none OFF
(will show only if present) Hi = High Alarm
Lo = Low Alarm
HL = High Limit
LL = Low Limit
dISP Display Input/Pen Value On = Display value On
during normal operation, OFF = Do not display value
RUN mode
dPOS Decimal Point Position 0 = nnnn 0
1 = nnn.n
2 = nn.nn
EUU Engineering Units that -9999 to 9999* 5000
equate to upper
transducer input
(will show only for Volt