Instruction Manual
III-20.2 F_Inp (frequency/counter input)
The frequency/counter input plugs into the modular options card C.The F_INP is used for configuration and parameter
setting of input F_INP. Input calculation is fixed to once per time slot.
Digital inputs:
reset a
1 = the value for Inp_a is reset to 0.
stop a
1 = the instantaneous value for Inp_a remains unchanged.
reset b
1 = the value for Inp_b is reset to 0.
stop b
1 = the instantaneous value for Inp_b remains unchanged.
Digital outputs:
slotid
0 = correct module fitted
1 = wrong module fitted
fail
1 = inserted module is detected, but no communication to the module.
z_a
signal status of HW input a
z_b
signal status of HW input b
ov_a
1 = frequency at HW input a exceeds the maximum permissible 20kHz
ov_b
1 = frequency at HW input b exceeds the maximum permissible 20kHz
Analog outputs
Inp_a
output value for channel a
Inp_b
output value for channel b
Configuration Description
Values Default
Func_a
DigInputr con
-
trol input
0
1
Count_1 r up counter
1
Count_2 r up/down counter
2
Count_3 r up/down counter with direction signal
3
Count_4 r quadrature signal
4
Frequenzr fre
-
quency measuring
5
Func_b
DigInputr con
-
trol input
0
1
Count_1 r up counter
1
Frequenz r frequency measuring
5
Time
for frequency measuring in seconds
0,1...20 10
9499-040-82711 Modular I/O - extension-modules
F_Inp (frequency/counter input) III-302
s
t
op a
0000
reseta
Inp_a
stop b
0000
resetb
Inp_b
a
b