Instruction Manual

III-18.2 OUT3 ( process output 3 (No. 118))
Function OUT3 is used for process output OUT3 configuration and parameter setting.
This analog output is provided only with hardware option C.
The function is firmly allocated to block number 83, it is calculated invariably in each time slot.
With digital input d1 used as signal source, it is switched over between 0 and 20mA as a output.
Analog input x1 used as signal source is taken to the continuous output linearly between x0 and x100 according
to configuration.
Inputs / outputs
Digital input:
d1
Input signal with digital signal conversion
Analog input:
x1
Input signal with analog signal conversion
Configuration parameters:
Parameter Description Values Default
Src
Signal source
Digital input d1
Digital
Analog input x1
Analog
t
Mode
Signal source action
direct/normally open
direct
t
inverse/normally closed
inverse
Type
Continuous output function
logic 0/20 mA
logic
0...20mA
0...20mA
t
4...20mA
4...20mA
x0
Analog input value x1 at 0%
-29 999 ... 999 999 0
x100
Analog input value x1 at 100%
-29 999 ... 999 999 100
Outputs 9499-040-82711
III-287 OUT3 ( process output 3 (No. 118))
HARDWARE
SOFTWARE
Logik
0..20mA
4...20mA
d1
x1
OUT3
Src
x0
x100
Type
Mode