Instruction Manual

Change mode (ramp/step)
If the shall change in a step or ramp is determined by a
parameter (Wmode) valid for all segments of a recipe (de
-
fault: ramp).
Ramp: The changes linearly from the start (end value of
previous segment) to the end value of the relevant seg
-
ment in time Tp. For the first segment, the following gra
-
dient is applicable: (Wp1 - Wp0)/Tp1
Step: The goes to value Wp immediately at segment start
and maintains it during segment time Tp.
9499-040-82711 Programmer
APROG ( analog programmer (No. 24)) / APROGD ( APROG data (No. 25)) III-209
Aus
Reset/Stop
Run
Start
Stop
Halt
(Run)
End
(Stop)
Preset
Run
Stop/Preset
Preset
Hand
Reset
F-Taste
F-Taste
F-Taste
F-Taste
Hand/Auto
Hand/Auto
F-Taste
Reset
Fig. 42 Statusdiagram of the programmer and the effect of the function key
Tp3
Wp3
Wp2
Wp3
Wp2
Segment 3
Start End
Tp2 Tp4
rampe
step
Parameter o
f
the segments
Wp0 Wp1 Wp2 Wp3 Wp4 Wp5
...
Tp1 Tp2 Tp3 Tp4 Tp5
...
Fig. 43