Instruction Manual

APROGD2
Analog inputs (APROGD2):
DBlock
Block number of cascaded data function `APROGD
Analog outputs (APROGD2):
DBlock
Own block number
Parameter
APROGD2
Description Value Range Default
ET Unit ET Unit
Type 1
(Type for segment 1) 0 Time segment tt
1 Gradient segment
2 Haltesegment
3 Sprungsegment
4 Time segment and wait at the end
5 Gradient segment and wait at the end
6 Hold segment and wait at the end
7 Step change segment and wait at the end
Typ10
Type for segment 10 like type 1 0 .. 7 ...
TpGr1
Time or gradient for segment 1 0 ... 59,999 0 ... 999:59 OFF —:—
Wp1
Final value for segment 1 -29999 ... 999999 -29999 ... 999999 0
.. .
TpGr10
Time or gradient for segment 10 0...59,999 0 ... 999:59 OFF —:—
Wp10
Final value for segment 10 -29999 ... 999999 -29999 ... 999999 0 0
Configuration
APROGD2
Description Value
PwrUp
Behaviour after mains
recovery
Continue program (default)
Prog.Fort
Search run in the actual segment
Fort.Seg.
Continue at actual time
Fort.Zeit
PEnd
Behaviour at program
end PEnd:
0 = Stop
1 = Reset
2 = Reset + Stop
(End-condition is reset
with stop)
stop after program end (default)
Stop
Reset after program end
Reset
Turbo
Time unit
Time = hours : minutes (default)
Std:Min
Time = minutes : seconds
Min:Sek
FKey
FKey (H key function):
0 = fkey output status switchover by H key (previous function)
1=H key used to generate a pulse at the fkey output (pulse length = 1 cycle)
2=H key controls the programmer (fkey output generates a pulse when
actuating the key, pulse length = 1 cycle)
Programmer 9499-040-82711
III-204 APROG ( analog programmer (No. 24)) / APROGD ( APROG data (No. 25))