Instruction Manual

III-13.1 C_KS8x (KS 800 and KS 816 node function - (No. 58))
Node function C_KS8x provides the interface to one of the multi-channel temperature controllers KS 800 or KS 816.
Analog outputs C1 C16 can be used to connect the KS8x functions, which represent each a controller of KS
800 (max. 8 controllers) or of KS 816 (max. 16 controllers).
Unlike the other KS 98-1 functions, only one data function can be soft-wired to each analog o utput.
Prerequisite for communication of KS98-1 multi-function unit and KS800 or KS816 is the complying adjustment of the
CAN parameters. (r see *1)).
Outputs
Analog inputs
C1...C16
Connection of the KS8x functions (single controllers in KS800 / KS816)
Digital outputs
et-err
0 = no engineering error 1 = engineering error (different node function at the same KS800)
id-err
0 = correct node
1 = faulty node Id (no KS800 / KS816 replied under the configured
node ID)
valid
0 = no data 1 = data were received
online
0 = KS800/816 is off-line 1 = KS800/816 is on-line
fail 1
0 = no fail at do1...do12 1 = fail at do1...do12
fail 2
0 = no fail at do13...do16 1 = fail at do13...do16
fail 3
0 = no heating current short circuit 1 = heating current short circuit
di1
di1status
di2
di2 status
di3
di3 status
di4
di4 status
Parameter und Konfigurationsdaten
Configuration Description Range Default
NodeId
KS800/KS816 node address
2...42 2
a
The data from the various controllers are read cyclically.
Maximally at intervals of 1.6 seconds (KS800) or 3.2 seconds (KS816), all data are updated.
*
1) The parameters for the CANopen bus are adjustable in engineering tool window "CANparameter” or via the
instrument parameters on the front panel (ET98 r Device r CANparameter).
Connection of KS 800 and KS 816 9499-040-82711
III-186 C_KS8x (KS 800 and KS 816 node function - (No. 58))