Instruction Manual
III-9.4 VPARA ( parameter operation (No. 98) )
General
Function VPARA provides an operating page which can be used for
changing max. 6 parameters of other function blocks available in the
engineering from the operating level.
Each parameter to be displayed is made known to the display function
with block number and parameter number by means of two configura
-
tion data. The engineering tool supports parameter setting by a special
operating sequence in which the parameter numbers of the selected
block are selected by means of the parameter descriptions (r see fig
-
ure opposite).
Additionally, an identifier and a unit text can be specified.
a
Values of the used analog inputs are stored as analog values,
when a positive flank is detected at the store input.
Activation of this input must be organized so that it occurs only
with relevant input value changes. Too frequent storage can
lead to EEPROM destruction.
9499-040-82711 Visualization
VPARA ( parameter operation (No. 98) ) III-164
VPARA
Y1
Y2
Y3
Y4
Y5
Y6
Bl-no
z1
z2
z3
z4
z5
z6
X1
X2
X3
X4
X5
X6
hide
lock
store
100 ts=11
store
lock
hide
Block1
Num1
Num3
Num5
Num2
Num4
Num6
Block2
Block3
Block4
Block5
Block6
X1
Y1
z1
y6
z6
.
.
.
.
.
.
.
.
Bl-no
X6
X5
X4
X3
X2
Fig. 23