Instruction Manual
Digital outputs
z1
d1, d2, d3. or d4
According to the input value of Select (or to values seld1, seld2) the relevant input variable is output.
Analog outputs
Casc
Cascade output = Select – 3.0
III-7.6 SELP ( parameter selection (No. 34))
Dependent of control signals d1 and d2, either one of the three preset parameters C1, C2, C3 or input variable x1 is
connected with output y1. Unused inputs are interpreted as 0 or logic 0.
Inputs/outputs
Digital inputs
d1
1st digital input for parameter selection
d2
2nd digital input for parameter selection
Analog input
x1
Input is output at y1, when d1 = 1 and d2 =1
Analog outputs
d1 d2
y1=C1
00
y1 = C2
01
y1 = C3
10
y1 = x1
11
Parameters:
Parameter Description Range Default
C1
1st constant, output at y1 with d1 = 0 and d2 = 0 . -29 999...999 999 0
C2
2nd constant, output at y1 with d1 = 0 and d2 = 1 . -29 999...999 999 0
C3
3rd constant, output at y1 with d1 = 1 and d2 = 0 . -29 999...999 999 0
9499-040-82711 Selecting and storage
SELP ( parameter selection (No. 34)) III-138
d1
d2
x1
001
012
103
114
y1
C2
C3
C1