Instruction Manual

III-6.8 TIME2 ( timer (No. 70) )
The function timer2 can only be used with real-time clock. With a positive flank at start, TIMER2 is started and
output z1 is switched to 1 after elapse of time TS and reset to 0 after elapse of time TE.
Example: TS.D =2,TS.H =1,TS.Mi=30 TE.D =0, TE.H =2,TE.Mi =2
After the change from 0 to 1 at input start, output z1 is set to 1 after 2 days, 1 hour and 30 seconds and reset to
0 after 2 hours and 2 seconds. Cyclic switching operations can be realized by feed-back of the end output to the
start input.
Inputs/outputs
Digital inputs
disabl
= 1 suppresses the switching operation.
reset
= 1 finishes an instantaneously running switching operation immediately.
start
= 1 switch-on duration start
Digital outputs
z1
= 1 switching operation running
end
= 1 switching operation end
Analog output
Week-D
indicates the actual weekday ( 0...6 = Su...Sa)
Parameters:
Parameter Description Range Default
TS.D
Switch-on delay day
0...255 0
TS.H
Switch-on delay hour
0...23 0
TS.Mi
Switch-on delay minute
0...59 0
TE.D
Switch-on duration days
0...255 0
TE.H
Switch-on duration hours
0...23 0
TE.Mi
Switch-on duration minutes
0...29 0
* 1) with the engineering tool broken rational numbers can be used; however only the integral
portion is taken over!
Time functions 9499-040-82711
III-133 TIME2 ( timer (No. 70) )
disabl
start
reset
end
z1
Week-D
TS.D
TS.H
TS.Mi
TE.D
TE.H
TE.Mi
t