11.7 Control algorithm
Text 1 Description Range Default
CPara
Controller parameters
Tpuls
Min. pulse length 0.1 ... 999.9 s 0.3
Tm
Actuator response time 10 ... 9999 s 30
Y2
Additional correcting value -105 ... 105 % 0
Ymin
Min. correcting variable limiting -105 ... 105 % 0
Ymax
Max. correcting variable limiting -105 ... 105 % 100
Y0
Correcting variable working point -105 ... 105 % 0
ParNr
Actual parameter set 0 ... 3
Xsd2
Switching difference of additional contact 0.1 ... 999.9 1
LW
Trigger point separation of additional contact -999 ... 9999 0
Xsd1
Switching difference of signaller 0.1 ... 999.9 1
Xsh2
Neutral zone (Xw > 0) 0.0 ... 999.9 % 0
Xsh1
Neutral zone (Xw < 0) 0.0 ... 999.9 % 0
Xsh
Neutral zone 0.2 ... 999.9 % 0.2
Set 0
Parameter set 0
Xp1 0
Proportional band 1 0.1 ... 999.9 % 100
Xp2 0
Proportional band 2 0.1 ... 999.9 % 100
Tn1 0
Integral action time 0 ... 9999 s 10
Tv1 0
Derivative action time 0 ... 9999 s 10
T1 0
Duty cycle 1 0.4 ... 999.9 s 5
T2 0
Duty cycle 2 0.4 ... 999.9 s 5
Set1
Parameter set 1
Xp1 1
Proportional band 1 0.1 ... 999.9 % 100
Xp2 1
Proportional band 2 0.1 ... 999.9 % 100
Tn1 1
Integral action time 0 ... 9999 s 10
Tv1 1
Derivative action time 0 ... 9999 s 10
T1 1
Duty cycle 1 0.4 ... 999.9 s 5
T2 1
Duty cycle 2 0.4 ... 999.9 s 5
Set2
Parameter set 2
Xp1 2
Proportional band 1 0.1 ... 999.9 % 100
Xp2 2
Proportional band 2 0.1 ... 999.9 % 100
Tn1 2
Integral action time 0 ... 9999 s 10
Tv1 2
Derivative action time 0 ... 9999 s 10
T1 2
Duty cycle 1 0.4 ... 999.9 s 5
T2 2
Duty cycle 2 0.4 ... 999.9 s 5
Set3
Parameter set 3
Xp1 3
Proportional band 1 0.1 ... 999.9 % 100
Xp2 3
Proportional band 2 0.1 ... 999.9 % 100
Tn1 3
Integral action time 0 ... 9999 s 10
Tv1 3
Derivative action time 0 ... 9999 s 10
T1 3
Duty cycle 1 0.4 ... 999.9 s 5
T2 3
Duty cycle 2 0.4 ... 999.9 s 5
Recov
Rapid Recovery (controller on)
XwOnY
X-W limit value (X-W < XWony Ä Y tracking) 0 ... 9999 * ‘——’
XwOnX
X-W limit value (X-W > XWonx Ä X tracking) 0 ... 9999 * ‘——’
GrwOn
set-point gradient with X tracking active 0,01 ... 99,99 /min ‘——’
* Decimal point position of adjustment range as for main variable X1.
Parameters
Operating instruction KS94 40