Owner's manual

11.2 Set-point function
Text 1 Description Range Default
Setpt
Set-point parameter
LC+
Band width upper limit 0...9999 ‘——’ (switched off)
LC-
Band width lower limit 0...9999 ‘——’ (switched off)
W0
lower set-point limit for Weff -999 ... 9999 0
W100
upper set-point limit for Weff -999 ... 9999 100
W2
additional set-point -999 ... 9999 100
Grw+
set-point gradient plus with W[w/min] 0.01 ... 99.99 ‘——’ (switched off)
Grw-
set-point gradient minus with W[w/min] 0.01 ... 99.99 ‘——’ (switched off)
Grw2
set-point gradient with W2[w/min] 0.01 ... 99.99 ‘——’ (switched off)
11.3 Time function
Text 1 Description Range
Timer
Timer-parameters
TS.Y
Start value: Year 0...255
TS.MD
Start value: Month and day Month:1...12; Day: 1...31
TS.HM
Start value: Hour and minutes Hour:0...23; Minutes: 0...59
TE.Y
Final value: Year 0...255
TE.MD
Final value: Month and day Month:1...12; Day: 1...31
TE.HM
Final value: Hour and minutes Hour:0...23; Minutes: 0...59
11.4 Programmer functions
Recp1
Programmer recipe 1
Analog Digital
Text 1 Description Range Def. Text 1 Description Range Def.
Wmode
Change mode 0: Ramp 0
D0
Reset value control output 1..4 0000..1111 0000
1: Step
Td1
Time segment 1 0...9999[min] ‘——’
2: Ramp (Time
priority
D1
control output 1..4 for segm. 1 0000..1111 0000
...
Pmode
Preset mode 0: Segment start 1
Td20
Time segment 20 0...9999[min] ‘——’
1: Program time
D20
control output 1..4 for segm. 20 0000..1111 0000
Pnext
Successive program 1..3 or ‘——’
LC-
Band width lower limit 0...9999
LC+
Band width upper limit 0...9999
Wp0
Reset value W0 -999...9999 0
TP1
Time segment1 0...9999 [min] ‘——’
WP1
Set-point segment 1 -999...9999 0
...
TP20
Time segment 20 0...9999 [min] ‘——’
WP20
Set-point segment 20 -999...9999 0
Recp2
see programmer recipe 1
Recp3
see programmer recipe 1
Parameters
Operating instruction KS94 38