Owner manual

q
Module A (process data of all 8 channels)
No. Descr. R/W
FIX point format
Rem.
Number of bytes
Value
Hex COM PROFIBUS
Inputs ] 66
0 Unit_State R 2 11 16DE
A
1 Xeff_1 R 2 50 1AE
2 Yeff_1 R 2 50 1AE
3 HC_1 R 2 50 1AE
4 Alarm_1 R 1 10 8DE
B
5 Status_1 R 1 10 8DE
C
6 Xeff_2 R 2 50 1AE
7 Yeff_2 R 2 50 1AE
8 HC_2 R 2 50 1AE
9 Alarm_2 R 1 10 8DE
B
10 Status_2 R 1 10 8DE
C
...
36 Xeff_8 R 2 50 1AE
37 Yeff_8 R 2 50 1AE
38 HC_8 R 2 50 1AE
39 Alarm_8 R 1 10 8DE
B
40 Status_8 R 1 10 8DE
C
Outputs ] 52
41 Unit_Cntrl W 4 23 32DA
D
42 Wvol_1 W 2 60 1AA
43 Yman_1 W 2 60 1AA
44 Cntrl_1 W 2 21 16DA
E
45 Wvol_2 W 2 60 1AA
46 Yman_2 W 2 60 1AA
47 Cntrl_2 W 2 21 16DA
E
...
63 Wvol_8 W 2 60 1AA
64 Yman_8 W 2 60 1AA
65 Cntrl_8 W 2 21 16DA
E
q
Module B (process data of all 8 channels + parameter channel)
No. Descr. R/W
FIX point format
Rem.
Number of bytes
Value
Hex COM PROFIBUS
Inputs ] 66
0 Unit_State R 2 11 16DE
A
1 Xeff_1 R 2 50 1AE
2 Yeff_1 R 2 50 1AE
3 HC_1 R 2 50 1AE
4 Alarm_1 R 1 10 8DE
B
5 Status_1 R 1 10 8DE
C
6 Xeff_2 R 2 50 1AE
7 Yeff_2 R 2 50 1AE
8 HC_2 R 2 50 1AE
9 Alarm_2 R 1 10 8DE
B
10 Status_2 R 1 10 8DE
C
...
36 Xeff_8 R 2 50 1AE
37 Yeff_8 R 2 50 1AE
38 HC_8 R 2 50 1AE
39 Alarm_8 R 1 10 8DE
B
40 Status_8 R 1 10 8DE
C
Process data
9 9499 040 50511