Owner manual

Rem. D Status 1 Tuning ‘State_Tune1’
MSB LSB
D7 D6 D5 D4 D3 D2 D1 D0
Bit no. Name Allocation Status ‘0’ Status ‘1’
D0
OStab Process at rest no yes
D1
Orun Optimization run off on
D2
Oerr Optimization result Ok error
D3...D5
‘0’ always ‘0’
D6
‘1’ always ‘1’
D7
Parity
Parameter a. configuration data
General
(function no.: 0)
Code Descr. R/W Type Description Range Rem.
B3 71 C100 R/W INT CFunc: Controller function
CType: Controller type
WFunc:set-point function
(T,H)
(Z)
(E)
0..xxyz
72 C101 R/W INT CMode:Controller output action
CDiff: x/x-w Differentiat.
CFail: Behaviour with sensor fail
CAnf: Start-up circuit
(T)
(H)
(Z)
(E)
0..wxyz
73 C700 R/W INT OMode:Optimization mode
OCond: Process at rest.
OGrp: Allocation group opt.
OCntr: Controlled adaptation mode
(T)
(H)
(Z)
(E)
0..wxyz
74 C180 R/W INT SWext: Source for Wext (T) 0..x000
Set-point
Set-point processing(function no.: 1)
Code Descr. R/W Type Description Range Rem.
B2 41 W0 R/W FP Min. set-point limit f. Weff -999..9999
42 W100 R/W FP Max. set-point limit f. Weff -999..9999
43 W2 R/W FP Additional set-point -999..9999
44 Grw+ R/W FP Set-point gradient plus >0..9.999
1)
45 Grw- R/W FP Set-point gradient minus >0..9.999
46 Grw2 R/W FP Set-point gradient W2 >0..9.999
Algo
Control algorithm (function no.: 3)
Code Descr. R/W Type Description Range Rem.
B2 41 Xsh R/W FP Neutral zone 0.2 .. 20,0 %
42 Tpuls R/W FP Min. pulse length 0.1..2,0 s
(1)
43 Tm R/W FP Actuator response time 10..300 s
44 Xsd1 R/W FP Switching difference signaller 0,1..9999 %
45 LW R/W FP Trigger point separation add. cont. -999..9999
46 Xsd2 R/W FP Switching difference add. cont. 0,1..9999 %
47 Xsh1 R/W FP Neutral zone 0.0 .. 999.9%
48 Xsh2 R/W FP Neutral zone 0.0 .. 999.9 %
Function block protocol
39 9499 040 50511
1) Datum has swich-off function; additional data value ‘-32000’