Owner manual

5.2.6 CONTR (FB no.: 50 ... 57 Type no.: 91)
All data which concern the controller are grouped in function block ‘CONTR’. They are available once for
each controller channel.
Process data
General
(function no.: 0)
Code Descr. R/W Type Description Range Rem.
00 Block R Block Block access (1...9)
1 Status 1 R ST1 Status 1
A
3 W R FP Eff. set-point
4 X R FP Eff. process value
5 Y R FP Effective output value
6 xw R FP Control deviation
13 Status Alarm x R INT Status x and Alarm x B1
18 Type R INT Type no. of function block 90
20 Block R Block Block access (21...26)
21 Xeff R FP Eff. process value
22 Yeff R FP Effective output variable
23 HC R FP Heating current measureement value
24 Unit_State R ICMP Input values (di) Ä page 12
25 Alarm_x R ICMP Alarm values Ä page 13 B2
26 Status_x R ICMP Status information Ä page 13
30 Block R Block Block access (31...38)
33 A/M R/W INT Automatic/manual switch-over 0..1
34 OStart R/W INT Optimization start 0..1
35 We/i R/W INT Wext/Wint switch-over 0..1
36 w/w2 R/W INT w/w2 switch-over 0..1
38 Coff R/W INT Controller off/on 0..1 C
Rem. A Status1: (code 01)
MSB LSB
D7 D6 D5 D4 D3 D2 D1 D0
Bit no. Name Allocation Status ‘0’ Status ‘1’
D0
Y1 Switching output off on
D1
Y2 Switching output off on
D2
A/M Auto/manual auto manual
D3
CFail Controller status ok not ok
D4
Coff Controller switched off no yes
D5
XFail Sensor fail no yes
D6
‘1’ always ‘1’
D7
Parity
Rem. B1 Status_alarm_x: Code 13
MSB LSB
D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0
Bit no. Name Allocation Status ‘0’ Status ‘1’
D0
w/w2 w/w2 switch over w w2
D1
we/wi extern/intern switch over extern intern
D2
w/wanf Start-setpoint switch over w wanf
D3
Orun Optimisation activ no yes
D4
A/M Automatic/Manuel switch over Auto Man
D5
Coff Controller off no yes
D6
Y1 Switchung output 1 off on
D7
Y2 Switching output 2 off on
D8
Lim HH Alarm HH off on
D9
Lim H Alarm H off on
D10
Lim L Alarm L off on
D11
Lim LL Alarm LL off on
D12
Fail Alarm sensor fail no yes
D13
HCAl Heating current alarm off on
D14
LoopAl Loop alarm off on
D15
"0" always "0"
Function block protocol