Owner manual

Rem. A Unit_State1
MSB LSB
D7 D6 D5 D4 D3 D2 D1 D0
Bit no. Name Allocation Status ‘0’ Status ‘1’
D0
‘0’ always ‘0’
D1
CNF Instrument status online configuration
D2...D4
‘0’ always ‘0’
D5
UPD Parameter update no yes
D6
‘1’ always ‘1’
D7
Parity
Rem. B DPErr
MSB LSB
D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0
Bit no. Name Allocation Status ‘0’ Status ‘1’
D0
Bus access not successful no error error
D1
Faulty parameter setting telegram no error error
D2
Faulty configuration no error error
D3
No more data exchange no error error
D4...D15
always ‘0’
Rem. C HWbas
COM2 0 0
TH Z E
Basic version without COM2
00 0 0
COM2 with CANopen
01 0 0
COM2 with PROFIBUS-DP
02 0 0
COM2 with ISO1745
03 0 0
Example: Value ‘HWbas = 0200‘ means that the addressed instrument has a COM2 interface with
PROFIBUS connection.
Rem. D SWopt
Version 0 0
TH Z E
Basic version
00 0 0
Water cooling (so far not available)
01 0 0
Rem. E SWCod
THZE
7th digit 8th digit 9th digit 10th digit
Example: Value ‘SWCod= 7239’ means that the software for the addressed instrument contains code
number 4012 157 239xx.
Rem. F SWvers
THZE
0 0 11th digit 12th digit
Example: Value ‘SWVers= 11‘ means that the software for the addressed instrument contains code number
4012 15x xxx11.
Rem. G UPD
Changing a parameter value or a configuration value via an interface is indicated in the UPD flag. After
power recovery, this bit is also set. The flag which can be read also via code UPD can be reset (value =0).
Rem. G2 HC_reset
Hc_reset = 0 normal
= 1 Reset of all heating currents
= 2 Starting a quicktest
= 3 Reset of all heating currents with following quicktest
After finishing of the chosen softwareroutine, the value of HC_reset is set 0 automatically.
Function block protocol
9499 040 50511 28