Owner manual
Rem. E Unit_Contrl II
MSB LSB
D31 D30 D29 ... ... D2 D1 D0
Bit no. Name Allocation Status ‘0’ Status ‘1’
D0
OUT17 Forcing of output OUT17 off on
D1
OUT18 Forcing of output OUT18 off on
D2
OUT19 Forcing of output OUT19 off on
D3
OstartG Start optimizing all group controllers no start start
D4
OStopG Forcing of output OUT5 no stop stop
D5
Dval Forcing of output OUT6 flank 0->1
D6- D15
always "0"
Rem. F Cntrl_x
MSB LSB
D15 D14 D13 ... ... D2 D1 D0
Bit no. Name Allocation Status ‘0’ Status ‘1’
D0
A/M Automatic/manual switch-over auto manual
D1
Coff Controller switched off no yes
D2
w/W2 w/W2 switch-over w W2
D3
We/w External/internal switch-over external internal
D4
OStart Start optimization
1)
no start start
D5
OStop Stop optimization
1)
no stop stop
D6 .. D15
unused, always ‘0’
Rem. G Digital_Outputs
MSB LSB
D15 D14 D13 ... ... D2 D1 D0
Bit-No. Name Allocation Status ‘0’ Status ‘1’
D0
Y1_7 Y1-Output Channel 7 off on
D1
Y2_7 Y2-Output Channel s 7 off on
D2
Y1_6 Y1-Output Channel 6 off on
D3
Y2_6 Y2-Output Channel 6 off on
D4
Y1_5 Y1-Output Channel 5 off on
D5
Y2_5 Y2-Output Channel 5 off on
D6
Y1_4 Y1-Output Channel 4 off on
D7
Y2_4 Y2-Output Channel 4 off on
D8
Y1_3 Y1-Output Channel 3 off on
D9
Y2_3 Y2-Output Channel 3 off on
D10
Y1_2 Y1-Output Channel 2 off on
D11
Y2_2 Y2-Output Channel 2 off on
D12
Y1_1 Y1-Output Channel 1 off on
D13
Y2_1 Y2-Output Channel 1 off on
D14
Y1_0 Y1-Output Channel 0 off on
D15
Y2_0 Y2-Output Channel 0 off on
Process data
9499 040 50511 14
1) Signals are active only with change from 0 Ä 1. The signal must be available, until a change of Orun
(see Status_x) has occurred.
2)See chapter 3.3 page 15 "Disabling mechanism with changes".