Owner manual
Rem. B1 Alarm_x
MSB LSB
D7 D6 D5 D4 D3 D2 D1 D0
Bit no. Name Allocation Status ‘0’ Status ‘1’
D0
Lim HH Alarm HH off on
D1
Lim H Alarm H off on
D2
Lim L Alarm L off on
D3
Lim LL Alarm LL off on
D4
Fail Alarm Sensor Fail no yes
D5
HCAl Heating current alarm off on
D6
LeckAl Leakage current alarm off on
D7
do1_8Al Alarm OUT1 ... 8 off on
Rem. C Status_x
MSB LSB
D7 D6 D5 D4 D3 D2 D1 D0
Bit no. Name Allocation Status ‘0’ Status ‘1’
D0
w/W2 w/W2 switch-over w W2
D1
We/w External/internal switch-over external internal
D2
w/Wanf Start-up set-point switch-over w Wanf
D3
Orun Optimization active no yes
D4
A/M Automatic/manual switch-over auto manual
D5
Coff Controller switched off no yes
D6
Y1 Switching output 1 off on
D7
Y2 Switching output 2 off on
Rem. D Unit_Contrl I
MSB LSB
D31 D30 D29 ... ... D2 D1 D0
Bit no. Name Allocation Status ‘0’ Status ‘1’
D0
OUT1 Forcing of output OUT1 off on
D1
OUT2 Forcing of output OUT2 off on
D2
OUT3 Forcing of output OUT3 off on
D3
OUT4 Forcing of output OUT4 off on
D4
OUT5 Forcing of output OUT5 off on
D5
OUT6 Forcing of output OUT6 off on
D6
OUT7 Forcing of output OUT7 off on
D7
OUT8 Forcing of output OUT8 off on
D8
OUT9 Forcing of output OUT9 off on
D9
OUT10 Forcing of output OUT10 off on
D10
OUT11 Forcing of output OUT11 off on
D11
OUT12 Forcing of output OUT12 off on
D12
OUT13 Forcing of output OUT13 off on
D13
OUT14 Forcing of output OUT14 off on
D14
OUT15 Forcing of output OUT15 off on
D15
OUT16 Forcing of output OUT16 off on
Process data
13 9499 040 50511