Owner manual

q
Module E (52 variable processdata and parameterchannel)
No.. Descr.. R/W
FIX Point-Format
Rem.
Number of
Bytes
Value
Hex COM PROFIBUS
Inputs ] 116
0 Unit_State, Digital_Outputs R 4 13 32DE
A, F
1 IN_1 … IN_8 R 16 57 8AE
2 IN_9 … IN_16 R 16 57 8AE
...
6 IN_41 … IN_48 R 16 57 8AE
7 IN_49 … IN_52 R 8 53 4AE
Outputs ] 116
8 Unit_Cntrl I, Unit_Cntrl II W 4 23 32DA
B
9 OUT_1 … OUT_8 W 16 67 8AA
10 OUT_9 … OUT_16 W 16 67 8AA
...
14 OUT_41 … OUT_48 W 16 67 8AA
15 OUT_49 … OUT_52 W 8 63 4AA
In- /Outputs
16 Parameterchannel R/W 8 / 8 F3 4AX
q
Module F (40 variable processdata and parameterchannel)
No.. Descr.. R/W
FIX Point-Format
Rem.
Number of
Bytes
Value
Hex COM PROFIBUS
Inputs ] 92
0 Unit_State, Digital_Outputs R 4 13 32DE
A, F
1 IN_1 … IN_8 R 16 57 8AE
2 IN_9 … IN_16 R 16 57 8AE
...
5 IN_33 … IN_40 R 16 57 8AE
Outputs ] 92
6 Unit_Cntrl I, Unit_Cntrl II W 4 23 32DA
B
7 OUT_1 … OUT_8 W 16 67 8AA
8 OUT_9 … OUT_16 W 16 67 8AA
...
11 OUT_33 … OUT_40 W 16 67 8AA
In- /Outputs
12 Parameterchannel R/W 8 / 8 F3 4AX
q
Module G (8 variable processdata and parameterchannel)
No.. Descr.. R/W
FIX Point-Format
Rem.
Number of
Bytes
Value
Hex COM PROFIBUS
Inputs ] 28
0 Unit_State, Digital_Outputs R 4 13 32DE
A, F
1 IN_1 … IN_8 R 16 57 8AE
Outputs ] 28
2 Unit_Cntrl I, Unit_Cntrl II W 4 23 32DA
B
3 OUT_1 … OUT_8 W 16 67 8AA
In- /Outputs
4 Parameterchannel R/W 8 / 8 F3 4AX
Process data