User guide
5.2 CODE tables
5.2.1
Structure of configuration words (C.xxxx)
The configuration words mentioned in the following code tables are composed of several sections, which can
be transmitted only in common.
The data in the table must be interpreted as follows:
Example (C100): Code Descr. R/W Type Description Range
71 C100 R/W INT CFunc: Controller function
Wfunc: set-point function
(T,H)
(E)
0..xxyz
Description CFunc WFunc
Thousands Hundreds Ones
Range
xxz
00 ... 07 0...1
Example: continuous controller; standard controller;
set-point-cascade with offset
0204
g
- For transmission of configuration words, see chapter page 29.
- Die Einstellmöglichkeiten der Konfigurationswörter entnehmen Sie der KS 800 Funktionsbeschreibung
(Best. Nr. 9499 040 49218)
5.2.2 INSTRUMENT (FB no.: 0 type no.: 0)
Function block ‘INSTRUMENT’ is used for classification of all data which are valid for the overall instrument.
Process data
General
(function no.: 0)
Code Descr. R/W Type Description Range Rem.
01 Unit_State 1 R ST1 Status 1
A
10 Block 13..18 R Block
13 Write Error R INT Error during last write access 0, 100...127
Ä p. 11
14 Write Error Position R INT Position of last write access error 0...99
15 Read Error R INT Error of last read access 0, 100...127
16 DPErr R INT Error message from DP-module
B
17 DPAdr_eff R INT Effectiv PROFIBUS adress 0 … 126
18 Type R INT Type no. of function block 0
20 Block 21...27 R Block
21 HWbas R INT Basic HW options: module A, P
C
23 SWopt R INT SW options 1
D
24 SWcod R INT SW code no. 7th to 10th digit of 12NC wxyz
E
25 SWvers R INT SW code no. 11th to 12th digit of 12NC 00xy
F
26 OPVers
1)
R INT Operating version
27 EEPVers
1)
R INT EEPROM version
31 OpMod R/W INT Switch over unit to configuration mode (only after 1) 0
Switch over unit to on-line mode (only after 0) 1
Cancelation of configuration mode (only after 0) 2
32 Ostartg R/W INT Self-tuning stop/start of all group controllers 0..1
33 UPD R/W INT Acknowledgement of local data change 0..1
G
Function block protocol
9499 040 49411 14
1) Data are specified for future use (distinction of internal version).