3263 ARRAY Min. cycle time 1 T1_1 FixedPoint1 rw 1.0
3264 ARRAY Proportional band 2 Xp2_1 FixedPoint1 rw 1.0
3265 ARRAY Integral time 2 Tn2_1 FixedPoint1 rw 1.0
3266 ARRAY Derivative time 2 Tv2_1 FixedPoint1 rw 1.0
3267 ARRAY Min. cycle time 2 T2_1 FixedPoint1 rw 1.0
Parameter and configuration data fct. no. 7
3270 ARRAY Proportional band 1 Xp1_2 FixedPoint1 rw 1.0
3271 ARRAY Integral time 1 Tn1_2 FixedPoint1 rw 1.0
3272 ARRAY Derivative time 1 Tv1_2 FixedPoint1 rw 1.0
3273 ARRAY Min. cycle time 1 T1_2 FixedPoint1 rw 1.0
3274 ARRAY Proportional band 2 Xp2_2 FixedPoint1 rw 1.0
3275 ARRAY Integral time 2 Tn2_2 FixedPoint1 rw 1.0
3276 ARRAY Derivative time 2 Tv2_2 FixedPoint1 rw 1.0
3277 ARRAY Min. cycle time 2 T2_2 FixedPoint1 rw 1.0
Parameter and configuration data fct. no. 10
32A0 ARRAY Max. output value Ya FixedPoint1 rw 1.0
32A1 ARRAY Start-up set-point Wa FixedPoint1 rw 1.0
32A2 ARRAY Start-up holding time TPa FixedPoint1 rw 1.0
FB alarm
Process data fct. no. 0
3300 ARRAY Alarm status 1 Status_AL1 Unsigned8 ro 1.0
3301 ARRAY Heating current alarm Status_AL2 Unsigned8 ro 1.0
3302 ARRAY Heating current measurement value HC FixedPoint1 ro 1.0
Parameter and configuration data fct. no. 0
3303 ARRAY Low limit alarm LimL FixedPoint1 rw 1.0
3304 ARRAY High limit alarm LimH FixedPoint1 rw 1.0
3305 ARRAY Switching difference high/low alarm xsd_2 FixedPoint1 rw 1.0
3306 ARRAY Low low limit alarm LimLL FixedPoint1 rw 1.0
3307 ARRAY High high limit alarm LimHH FixedPoint1 rw 1.0
3308 ARRAY Heating current limit value LimHC FixedPoint1 rw 1.0
3309 ARRAY Src: signal source (T,H) C600
Fnc: function (Z)
Unsigned16 rw
*
1.0
330A ARRAY Alarm target C601 Unsigned16 rw
*
1.0
330B ARRAY Alarmsource/-function L, C602 Unsigned16 rw
*
3.0N
330C ARRAY Alarmsource/-function H, C603 Unsigned16 rw
*
3.0N
330D ARRAY Alarmsource/-function HH, C604 Unsigned16 rw
*
3.0N