Owner manual

10.2 Configurations
Dependent on device version und adjusted configurations values not needed become hidden.
µ Entrys marked with this symbol are selectable only with existing device-option.
Controller Cntr
Name Value range Description
SP.Fn
setpoint processing
0
Setpoint/ ext. Setpoint
1
program controller
2
timer mode 1
3
timer mode 2
4
timer mode 3
5
timer mode 4
6
timer mode 5
7
timer mode 6
8
standard + SP-E
9
programmer + SP.E
b.ti
0...9999
timer tolerance
C.tYP
process value processing µ
0
process value = x1
1
ratio controller (x1+oFFS)/x2
2
difference (x1 - x2)
3
max (x1, x2)
4
min (x1, x2)
5
mean value (x1, x2)
6
Switch-over (x1, x2)
7
Oxygen measurement with const. probe temperature
8
Oxygen measurement with measured probe temperature
C.Fnc
control behaviour
0
signaller (on/off controller)
1
PID controller (2-point and continuous)
2
D/Y switch-over
3
2 x PID (3-point and continuous)
4
3-point stepping controller
mAn
automatic/manual switching
0
Manual operation not permitted
1
Manual operation admitted
C.Act
direction of operation
0
inverse, e.g. heating
1
direct, e.g. cooling
FAIL
behaviour at sensor break
0
outputs off
1
switch to Y2
2
mean correcting value
rnG.L
lower control range [phys]
rnG.H
upper control range [phys]
Adt0
Tuning of cycle time
0 automatische Optimierung
1 keine Optimierung
Configuration level
Configurations 54 KS 45