Owner manual

9.3 Starting the timer
Dependent of configuration, the timer start is as follows:
at controller switch-on (power-on)
by adjusting the timer t.ti > 0 (at
extended operating level)
by a positive edge at digital input di1 with
configured SP r SP.2 or Y2 r Y
switch-over.
via the serial interface.
Display: the timer run is indicated by texts on LCD line 2,
which appear alternately with the other displays:
g
With active timer, the time can be adjusted by changing parameter t.ti at extended operating level.
g
The status of an active timer can be output (Conf / Out.x / timE). A timer is set when started and
reset by elapsing or cancelation.
9.4 End / cancelation of the timer
The timer can be canceled. After elapse of the timer, the controller continues operating using the function dependent
on operating mode.
Cancelation is possible by:
changing the timer setting t.ti = 0 (at extended operating level)
switching over digital input di1 (SP.2 r SP or Y r Y2 switch-over) configured as a push-button).
via the serial interface
g
If the digital input is defined as a switch or if the Func function with SP/SP2 or Y/Y2 switch-over is
configured, the signal change will cancel the timer.
Timer
KS 45 51 Starting the timer
LCD-display 2 Signification
.r.u.n.
timer is started
timer is not running yet
run
timer is started
timer is running
End
Timer elapsed
Timer canceled
off deletion of End display by pressing any key
timer is off
1
2
ME
450.3
run
äüüü