Owner manual

9.1.2 Tolerance band
Timer modes 1,2 and 6 are provided with a freely adjustable tolerance band. The tolerance band around the set-point
can be adjusted via parameter b.ti in the Conf menu (x = SP.2 _ b.ti )
(r page 53)
9.1.3 Timer start
Various procedures for starting the timer are possible:
g
When using the digital input as a switch (di.Fn=0/1)orwhen using the Func switch-over function, the
timer is re-started automatically after elapsing. Switch-over, e.g. opening, will cancel the timer function.
g
Using the Func function as a switch for starting the timer is not recommendable, because the timer would
be re-started immediately after elapsing.
9.1.4 Signal end
If one of the relays shall switch after timer elapse, parameter TimE = 1 and inverse action O.Act = 1 must be
selected for the relevant output OUT.1 OUT.3 in the ConF menu (r page 57, 58). If direct action is selected,
the relevant output signals the active timer.
9.2 Determining the timer run-time
The timer run-time can be determined via parameter t.SP in the PArA menu. The timer run-time must be specified
in minutes with one digit behind the decimal point (0,1 minutes = 6 seconds).
Alternatively, the timer run-time can be determined directly at extended operating level (r chapter 9.3).
Timer
Determining the timer run-time 50 KS 45
Start via LOGI Mode
Y2
=
SP.2
=
123456
Y2 r Y switching via digital input di1 1 2xddddd-
SP r SP.2 switching via digital input di1 1 x 2-----d
Power On 0 x ddddd-
x 0-----d
Changing t.ti>0 (extended operating level) x x dddddd
Serial interface (if provided) x x dddddd
Operation via BlueControl
Ò
(online operation) x x dddddd
1
when using a digital input, adjust parameter di.Fn = 2 ( ConF/ LOGI) ( key function)
x no effect
- not applicable