Owner manual

6.10 Resetting to factory setting
In case of faulty configuration, the device can be reset to the default manufacturers condition.
1
For this, the operator must keep the
keys increment and decrement
pressed during power-on.
2
Then, press key increment to select
YES.
3
Confirm factory resetting with Enter
and the copy procedure is started
(display
COPY).
4
Afterwards the device restarts.
In all other cases, no reset will occur
(timeout abortion).
g
If one of the operating levels was
blocked in BlueControl
Ò
, reset to
factory setting is not possible.
g
If a pass number was defined (via
BlueControl® ), but no operating
level was blocked, enter the correct
pass number when prompted in 3.A
wrong pass number aborts the reset
action.
g
The copy procedure ( COPY) can
take some seconds.Now, the
transmitter is in normal operation.
Afterwards the device restarts as usual.
Functions
Resetting to factory setting 34 KS 45
FAC
torY
FAC
no
+ Power on
FAC
yEs
ô
FAC
COPY
8.8.8.8
#:#:#:#:#
ääää
1
2
3
4
Error-Status
Beschreibung Verhalten
0
kein Fehler
3
falsche Wirkungsrichtung Regler umkonfigurieren (invers i direkt)
4
keine Reaktion der Regelgröße eventuell Regelkreis nicht geschlossen: Fühler,
Anschlüsse und Prozeß überprüfen
5
tiefliegender Wendepunkt obere Stellgrößenbeschränkung Y.Hi vergrößern
(ADA.H) bzw. untere Stellgrößenbeschränkung Y.Lo
verkleinern (ADA.C)
6
Sollwertüberschreitungsgefahr
(Parameter ermittelt)
eventuell Sollwert vergrößern (invers), verkleinern (direkt)
7
Stellgrößensprung zu klein
({y > 5%)
obere Stellgrößenbeschränkung Y.Hi vergrößern
(ADA.H) bzw. untere Stellgrößenbeschränkung Y.Lo
verkleinern (ADA.C)
8
Sollwertreserve zu klein Sollwert vergrößern (invers), verkleinern (direkt)
oder Sollwerteinstellbereich verkleinern
(r PArA/ SEtp/ SP.LO und SP.Hi )