Instruction Manual

1 Mounting
Safety switch:
For access to the safety switches, the controller must be withdrawn from the hou
-
sing. Squeeze the top and bottom of the front bezel between thumb and forefinger
and pull the controller firmly from the housing..
1 Factory setting 2 Default setting: display of all levels
suppressed, password PASS = OFF
a
Safety switch 10V i mA/Pt always in position left or right. Leaving the
safety switch open may lead to faulty functions!
l
Caution! The unit contains ESD-sensitive components.
Mounting
Operating KS4x-1 5
or:
%
max.
95% rel.
max.
60°C
0°Cmin.
96 (3.78")
48 (1.89")
Loc
10V i mA/Pt
min.48
(1.89")
10
(0.4")
1..10
(0.04..0.4")
118
(4.65")
45
+0,6
(1.77" )
+0.02
92
+0,8
(3.62" )
+0.03
KS 40-1 universal
125
126
SP.X
run
Err
Ada
*
Ü
*
Ü
Loc 10V mA/Pt
Loc 10V mA/Pt
Loc 10V mA/Pt
Safety switch
KS 42-1 universal
125
126.
SP.x
run
Err
A
da
da
96 (3.78")
96
(3.78")
Front view KS42-1
KS 41-1 universal
125
126.
SP.x
run
Err
Ada
48 (1.89")
96 (3.78")
Front view KS41-1
10V i mA/Pt right 1 Current signal / Pt100 / thermocouple at InP.1
left Voltage signal at InP.1
Loc open Access to the levels is as adjusted by means of BlueControl
(engineering tool)
2
closed 1 all levels accessible wihout restriction