Instruction Manual

8.1.4 Signal end
If one of the relays shall switch after timer elapse, parameter TimE = 1 and in
-
verse action O.Act = 1 must be selected for the relevant output OUT.1
OUT.3 in the ConF menu (r page 25, 26). If direct action is selected, the rele
-
vant output signals the active timer.
8.2 Determining the timer run-time
The timer run-time can be determined via parameter t.SP in the PArA menu.
The timer run-time must be specified in minutes with one digit behind the deci
-
mal point (0,1 minutes = 6 seconds).
Alternatively, the timer run-time can be determined directly at extended opera
-
ting level (r chapter 8.3).
8.3 Starting the timer
Dependent of configuration, the timer start is as
follows:
w
by a positive flank at one of digital inputs
di1..3
w
by pressing key Ò
w
by switching on the controller (power On)
w
by changing the timer run-time t.ti >0
(extended operating level)
w
via the serial interface
Display:
g
With active timer, the time can be adjusted by changing parameter t.ti at
extended operating level.
Timer
Determining the timer run-time 48 Operating KS4x-1
125
126
SP.x
run
Ada
Err
Run LED Signification
blinks
-
timer was started
-
timer is not running yet
lit
-
timer was started
-
timer is running
off
( End and setpoint are
displayed alternately)
-
timer is off
-
timer has elapsed
-
deletion of End display by pressing any
key