Instruction Manual

Offset correction ( ConF/ InP.1 / Corr =1 ):
InL.1: The input value of the scaling point is displayed.
The operator must wait, until the process is at rest.
Subsequently, the operator acknowledges the input value by pressing
key Ù.
OuL.1: The display value of the scaling point is displayed.
Before calibration, OuL.1 is equal to InL.1.
The operator can correct the display value by pressing keys ÈÌ .
Subsequently, he confirms the display value by pressing key Ù.
Calibration level
42 Operating KS4x-1
r
Ì
Ù
3sec.
r
PArA
CAL
r
Ù
r
InP.1
Ù
r
InL.1
r
r
Ù
r
:
OuL.1
r
r
Ù
End
r
r
Ù
Ì
È
125
126
SP.X
run
Err
Ada