User guide
Configuration level
19 KS40-1 burner
Name Value range Description Default
Own
setting
FAIL
Behavior at sensor break
1
0
Controller outputs switched of
1
y=Y2
2
y = mean output. The maximum permissible output can be adjusted with
parameter Ym.H. To prevent determination of inadmissible values, mean value
formation is only if the control deviation is lower than parameter L.Ym.
rnG.L
-1999...9999
X0 (low limit range of control) 1
0
rnG.H
-1999...9999
X100 (high limit range of control) 1
100
1 rnG.L and rnG.H indicate the control range to which e.g. self-tuning is related.
InP.1
Name Value range Description Default
Own
setting
S.tYP
Sensor type selection
50
0
Thermocouple type L (-100...900°C) , Fe-CuNi DIN
1
Thermocouple type J (-100...1200°C) , Fe-CuNi
2
Thermocouple type K (-100...1350°C), NiCr-Ni
3
Thermocouple type N (-100...1300°C), Nicrosil-Nisil
4
Thermocouple type S (0...1760°C), PtRh-Pt10%
5
Thermocouple type R (0...1760°C), PtRh-Pt13%
20
Pt100 (-200,0 ... 100,0 °C)
21
Pt100 (-200,0 ... 850,0 °C)
22
Pt1000 (-200,0...200,0 °C)
23
KTY 11-6 (special 0...4500 Ohm)
30
0...20mA / 4...20mA 2
40
0...10V / 2...10V 2
50
Potentiometer 0...160 Ohm 2
51
Potentiometer 0...450 Ohm 2
52
Potentiometer 0...1600 Ohm 2
S.Lin
Linearization (only at S.tYP = 30 (0..20mA) and 40
(0..10V) adjustable)
0
0
None
1
Linearization to specification. Creation of linearization table
with BlueControl (engineering tool) possible. The characteristic
for KTY 11-6 temperature sensors is preset.
Corr
Measured value correction ( scaling
2
0
Without scaling
1
Offset correction (at CALlevel)
2
2- point correction (at CALlevel)
3
Scaling (at PArA level)
2 With current, voltage or potentiometer input signals, scaling is required (see section 5.1).