User guide

4.2 Configuration without qUIC ( qUIC= OFF)
When key Ù is kept pressed during controller supply voltage switch-on, the
configuration is switched off with qUIC.
Now, all configuration settings are available to the user.
For changing back to configuration with qUIC , the two keys ÌÈmust be
kept pressed during controller supply voltage switch-on.
a
Hereby, the controller is reset to the factory-set default values !
4.3
Configuration survey:
Configuration level
KS40-1 burner 18 Configuration without qUIC ( qUIC= OFF)
Con1
Name Value range Description Default
Own
setting
Con1
0000...2330 qUIC - Configuration
0000
Wire hook switches (on electronic card)
Name Value range Description Default
Own
setting
Loc
open or closed Wire hook switch for locking the ConF- and PArA- level (if
enabled with BlueControl)
closed
InP.1
mA/Pt or 10V Wire hook switch for chosing InP.1 signal type
mA/Pt
Cntr
Name Value range Description Default
Own
setting
SP.Fn
Basic configuration of setpoint processing
0
0 set-point controller can be switched over to external set-point (->
LOGI/ SP.E)
1 programmer
8 standard controller with external offset (SP.E)
C.Fnc
Control behavior (algorithm)
0
0
2-point signaller
1
PID controller (2-point and continuous)
2
D/ Y/Off, or 2-point controller with partial/full load switch-over
3
2 x PID (3-point and continuous)
4
3-point stepping controller
7
3-point signaller
8
3-point stepping controller switchable to signaller
9
3-point stepping controller switchable to 3-point signaller
mAn
Manual operating permitted
1
0
no
1
yes (see also LOGI/ mAn)
C.Act
Method of controller operation
0
0
Inverse, e.g. heating
1
Direct, e.g. cooling