DataVU 7 - Operating Manual 59484
Menu structure of the paperless recorder v Chapter 8 "Device Manager" v Chapter 7 "Memory Manager" v Chapter 6 "Alarm and Event Lists" v Chapter 4 "Visualization" v Chapter 5 "Memory Presentation (History)"
Contents 1 Introduction 9 1.1 Preface ........................................................................................................ 9 1.2 Arrangement of the Documentation ...................................................... 10 1.3 Typographical Conventions .................................................................... 12 2 Instrument Description 2.1 Displays and Controls ............................................................................. 17 2.2 Analog Inputs ......
Contents 3.3 Group and Plant Management (Batches) ............................................... 50 4 Visualization 4.1 Activating the Operator Level ................................................................. 53 4.2 Overview of Header Lines ....................................................................... 54 4.3 Curve Presentation .................................................................................. 55 4.4 Bar Graph Presentation .........................................
Contents 8.5 Configuration ............................................................................................ 90 8.6 Parameterization ...................................................................................... 90 8.7 Service ...................................................................................................... 91 9 Parameterization 9.1 Fine calibration ......................................................................................... 94 9.
Contents 16 Configuration - External Analog Inputs 117 16.1 Range Start … Alarm Configuration .................................................... 117 16.2 Alarm configuration ............................................................................... 118 16.2.1 Status … Alarm text 2 .............................................................................. 118 16.2.2 Alarm rejection .........................................................................................
Contents 21.4 Range Start … Alarm Configuration .................................................... 151 21.5 Alarm Configuration .............................................................................. 152 22 Configuration - Interface 22.1 Ethernet .................................................................................................. 156 155 22.2 RS232/RS485 .......................................................................................... 158 22.2.1 General .............
Contents 26.3 Entering values ....................................................................................... 183 26.3.1 Whole numbers (integers) ........................................................................ 183 26.3.2 Real numbers (floating point) ................................................................... 184 27 Web server 185 27.1 General .................................................................................................... 185 27.
1 Introduction 1.1 B Preface Please read this manual before commissioning the instrument. Keep the instructions in a place which is accessible to all users at all times. Please assist us in improving these instructions where necessary. Your comments will be appreciated.
1 Introduction 1.2 Arrangement of the Documentation The documentation for this instrument is addressed to equipment manufacturers (OEMs) and users with appropriate technical expertise. It consists of the following parts: Instrument documentation in printed form 59486 Operating instructions The operating instructions are an extract from the operating manual and cover the basic operation of the paperless recorder.
1 Introduction 59488/59490 Installation instructions The installation instructions describe the installation of the recorder and the connection of the supply and signal cables. The instructions also contain a list of the technical data. 59492 59488 Installation instructions for recorder with zinc die-cast panel 59490 Installation instructions for recorder with stainless steel panel Setup program These instructions describe the functions of the setup program.
1 Introduction 1.
1 Introduction Presentation modes Screen texts Program manager Texts that are displayed in the setup program are indicated by italic script. Menu items Edit Device data Menu items in the setup and instrument software referred to in this operating manual are shown in italics. Menu name, menu item and submenu item are separated from each other by “”.
1 Introduction 14
2 Instrument Description Power supply Inputs/outputs 0…18 analog inputs max. 0…24 binary inputs/outputs max. AC 100...240V +10/-15%, 48...63Hz AC/DC 20...30V, 48...
2 Instrument Description Device features 16 Front panel Zinc die-cast with lid Stainless steel (enclosed) Interfaces locatesd on front panel 2x USB None External memory CF-card located on front panel, maximum 4 GB None Operation Control knob Touchpad Interfaces located on device‘s rear 2x USB, 1x RS232/RS485, 1x RS232, 1x Ethernet, 1x PROFIBUS-DP (option) 2x USB, 1x RS232/RS485, 1x RS232, 1x Ethernet, 1x PROFIBUS-DP (option) Special features Tested acc.
2 Instrument Description 2.1 Displays and Controls Recorder with zinc die-cast panel Power LED (green) is on continuously as soon as power is applied. TFT color display 320 x 240 pixels, 256 colors Status LED (red) is on continuously if an alarm is present. Cover for the CompactFlash® slot1 and the setup plug connection Control knob The control knob is used to configure and operate the paperless recorder. It can be rotated in both clockwise and anti-clockwise directions, and pressed. 1.
2 Instrument Description Recorder with zinc die-cast panel Status & title bar Numerical measurement display Visualization window (diagram) Header USB host for data exchange (measurement data, configuration data, user lists) between the recorder and the PC CompactFlash slot for data exchange (measurement data, configuration data, user lists) between the recorder and the PC 18 USB device for communication with the setup program or PCC Ejector for the CompactFlash memory card Signal LED Light is on duri
2 Instrument Description Recorder with stainless steel panel Power LED (green) is on continuously as soon as power is applied. TFT color display 320 x 240 pixels, 256 colors Status LED (red) is on continuously if an alarm is present. Touchpad The touchpad is used to configure and operate the recorder. A circular motion with a finger at the outer edge has the same effect as the turning of the control knob. Tapping the middle of the touchpad has the same effect as when the control knob is pressed.
2 Instrument Description 2.2 Analog Inputs Internal analog inputs The paperless recorder can be equipped with 0 to 18 analog inputs. During configuration, they are designated Analog input 1 — 18. There are two ways of finding out the exact number of analog inputs that have been integrated: - Check the type code on the nameplate against the type designation. Please refer to the Installation Instructions 59488 for an explanation of the nameplate and type designation.
2 Instrument Description 2.3 Binary Inputs/Outputs Internal binary inputs/ outputs The recorder can be equipped with 0, 8, 16 or 24 binary inputs/outputs. During configuration, they are designated Binary input/output 1 — 24. The function (input or output) can be configured. There are two ways of finding out the exact number of binary inputs/outputs that have been implemented: - Check the type code on the nameplate against the type designation.
2 Instrument Description 2.4 Relay Outputs A maximum of 7 relays (1 as standard, 6 as an extra) is available to signal, for instance, alarms or limit infringements. The action can be configured as break (SPST-NC) or make (SPST-NO) contact. There are two ways of finding out whether the 6 additional relays are available: - Check the type code on the nameplate against the type designation. Please refer to the Installation Instructions 59488 for an explanation of the nameplate and type designation.
2 Instrument Description 2.5.1 Counter Counter inputs - Binary inputs - Alarms - Errors - ... v Chapter 2.7 “Binary Signals” Counting frequency 8Hz max. Weighting Counted pulses are weighted by multiplying them by a factor. A down counter can be implemented by entering a negative weighting (e.g. weighting factor -1). 2.5.2 Integrators Integrator inputs - Analog inputs Integrator time base - sec, min, hr and day Weighting Integrators are weighted by multiplying them by a factor.
2 Instrument Description 2.5.3 Operating time counter The operating time counter will count how long a selected binary input or one of the binary signals is closed. The time can be displayed in sec, min, hr and days. 2.5.4 High-speed counters Counter inputs The first two binary inputs of each module (B1, B2, B9, B10, B17, B18) can be counted. Binary inputs are available if the module is fitted with 3 analog inputs and 8 binary inputs. Counting frequency Max.
2 Instrument Description 2.5.6 Recording period of the counts For all counters, integrators, operating time counters, and high-speed counters, the counters are concluded and the counter states are stored and restarted after an adjustable amount of time (recording time period). The counter states of the most recently completed recording period can be numerically displayed.
2 Instrument Description 2.5.7 Reset counters Periodic reset There is a recording time period for each counter, integrator, operating time counter and high-speed counter. At the end of this period, the current data (value and time) are saved and the value reset to 0. Then the next time period is recorded. The overall and annual counters/integrators are an exception. These are saved whenever any count/integration has been completed, but not reset to 0.
2 Instrument Description 2.5.9 Response to instrument reconfiguration When the instrument is reconfigured, the current counter/integrator recording periods remain unaffected. The counter/integrator values will not be reset to 0 and the recording period will not be restarted. H The values can be deliberately reset, via the “Parameterization” menu. 2.5.
2 Instrument Description 2.6 Math/Logic Module The math and logic module is available as an extra. Like the counters/ integrators, the math and logic module are channels that are not available as hardware but are calculated by the instrument software. The math and logic module consists of two parts: - the math module for calculating analog values and - the logic module for linking Boolean values (0 or 1). Math module The math module provides 18 measurement inputs for calculating new “virtual” channels.
2 Instrument Description The following fixed functions are available: - difference - ratio - relative humidity - moving average For the moving average, the reference channel has to be entered (in most cases, the analog input) and the time (in minutes). They will be used to calculate the moving average. The following operators and functions are available for formulas: +, -, *, /, (, ), SQRT(), MIN(), MAX(), SIN(), COS(), TAN(), **, EXP(), ABS(), INT(), FRC(), LOG(), LN().
2 Instrument Description Following are some of the variables available for formulas: - Binary inputs - Logic channels - Alarms - Errors These functions can be used for formulas: - ! & | ^ / \ ( ) H 30 (NOT) (AND) (OR) (XOR) (rising edge) (falling edge) (open bracket) (close bracket) Further information can be obtained from the instructions on the setup program (59492).
2 Instrument Description 2.7 Binary Signals Binary signals are used by the recorder, forexample to - operate a relay, - activate the Event operating mode, - start external reports and - start batch reports. Binary signals are made visible as binary traces or switch symbols and can be used as a basis for counters. The binary inputs (internal and external) are binary signals. Binary I/O The switching states of the internal binary inputs/outputs are indicated by the binary signals.
2 Instrument Description Alarms, analog inputs The alarm monitoring states of the internal analog inputs are indicated by the binary signals. Depending on the instrument hardware level, up to 18 internal analog inputs are available. There are two binary alarm signals for each analog input. v Chapter 13 “Configuration - Analog Inputs” Alarms, counters/integr. The alarm monitoring states of the counters/integrators are indicated by the binary signals. 27 counters/integrators are available.
2 Instrument Description Signal Description CF card full The signal is activated when the memory space of a CF card that has been inserted (external memory) has fallen below the selected threshold value. v Chapter 2.10 “Reading out Data” Mem.al. interface The signal is activated when the device-internal memory space available for data readout via interface has fallen below the selected threshold value. v Chapter 2.10 “Reading out Data” (Mem.al.
2 Instrument Description 2.8 Operating Modes 2.8.1 Normal, Timed, and Event Mode The operating modes are used to determine the cycle in which measurement data are stored.
2 Instrument Description Active operating mode The active operating mode is shown in the diagram by different symbols behind the current display for the diagram speed: Operating mode Symbol Normal operation Timed mode Event mode 2.8.2 Eco mode The parameters for Eco mode are set in the menu for normal operation. However, Eco mode can be used for all three operating modes.
2 Instrument Description If the measurements go outside the tolerance band, and the new measurement, which is outside the tolerance band, is present for at least the duration of the storage cycle that was set in the active operating mode, then it is acquired and stored and a new tolerance band is applied. t2 t3 t6 t5 t1 t4 10s 10s 10s 10s 10s 10s 10s 10s 10s t t1 = storage through “Min. storage cycle” (forced storage) and application of a new tolerance band.
2 Instrument Description 2.9 Data Storage Operating principle A/D 2 A/D 1 CPU (SRAM) Internal memory 20 kB 20 kB 20 kB 20 20 kB kB External CompactFlash memory card Analog inputs Data recording Measurements are acquired continuously in a 125msec sampling cycle. Based on these measurements, reports are compiled and limits checked.
2 Instrument Description Data security The data are stored in coded form in a proprietary format. This ensures a high level of data security. If the CompactFlash card is removed from the instrument, no data will be lost immediately, as these data are still stored in the internal memory. A loss of data will only occur if, after the CompactFlash card has been removed, internal memory is completely rewritten as well, and no data have been read out through the interface.
2 Instrument Description 2.10 Reading out Data In addition to automatic read-out via the CompactFlash memory card, measurement data can also be read out through one of the interfaces (RS232, RS485, USB device, Ethernet) and with a memory stick (USB host). The options for reading a CF card/memory stick and interface work in a parallel manner. For this reason, there are also two “binary signals”, which indicate when the available storage space has fallen below a certain configurable value.
2 Instrument Description Readout via interface Use the PCA Communications software PCC to read out measurement data via the serial or USB device or Ethernet interface. H Use the same archive (in the PC) for reading out data via the interface as for a readout via the CF card. This saves having to put together data from different files at a later date. v Please refer to the Operating Manual 59500 for further information. 2.
2 Instrument Description Open archive Evaluation software PCA3000 v Please refer to the Operating Manual 59498 for further information.
2 Instrument Description 42
3 Operating Principle 3.1 Operating Principle and Graphic Elements Header Fixed functions Variable functions with changing symbols Function is activated when the control knob is pressed. The functions of the paperless recorder are selected in the header. The selected function is indicated by a blue background. Recorder with control knob - Function selection by rotating the control knob (to right or left). - Function is activated by pressing the control knob.
3 Operating Principle diagram (curve display) has been selected.
3 Operating Principle Status and title bar This line (bar) shows alarm and error messages, as well as general information, and information about the active representation mode (e.g. sampling rate). It is automatically blanked out by the system, if necessary. If the text is shown in red, this indicates an error message. Sampling rate and operating mode = normal mode = event mode = timed mode Data are currently being read by the PCA Communications software PCC.
3 Operating Principle Numerical measurement display (diagram view) The numerical measurement display is available for the presentation modes: - Curves, - history (of the curve presentation) and - digital diagram available. In the curve presentation, the numerical display can be switched on or off. This switching on or off also applies to the history presentation. An alarm for a channel is shown in red (HIGH alarm) or orange (LOW alarm). The colors can be configured in the setup program.
3 Operating Principle Visualization window (diagram) Symbols for data acquisition: Comment has been entered Event occurred Alarm is no longer present Alarm has been signaled In the visualization window, the measurement data are shown in graphical form. Alarms are indicated by a red or orange color for the curve (can be configured in the setup program). Communication with the operator (device configuration, checking alarm and event lists etc.) also takes place via the visualization window.
3 Operating Principle 3.2 Operating Example Start The normal display is active. Operation h Select the operator level by rotating the control knob. h Activate the operator level by pressing the control knob.
3 Operating Principle h Select the operator level by rotating the control knob. h Activate the bar graph presentation by pressing the control knob. Result The bar graph presentation starts.
3 Operating Principle 3.3 Group and Plant Management (Batches) Within the recorder, all analog inputs, binary inputs, counters and integrators, are collected together into groups. A maximum of nine groups is available as a total. Each group can consist of a maximum of 6 analog inputs, 6 binary inputs (or outputs), and 4 counters/integrators. The visualization and storage of the analog inputs and binary inputs (outputs) is always made on a group basis.
3 Operating Principle A In order for a batch to be usable, its main group must be active (status = “Display” or “Display, save”) and at least one analog channel in the group must be assigned. Batch for plant Main group 1 1 2 4 3 7 The number of plants is configured through the parameter Device manager Configuration Batches/plants Gen. plant parameters Number of plants.
3 Operating Principle 52
4 Visualization 4.1 Activating the Operator Level The type of visualization (curve presentation, bar graph etc.) is selected at the operator level. Note that the appearance of the operator level can be influenced by the configuration. h Select the operator level by rotating the control knob. h Activate the operator level by pressing the control knob. Operator level You can alter the visualization after activating the operator level.
4 Visualization 4.2 Overview of Header Lines Curve presentation (diagram) Bar graph presentation Text picture presentation Process image presentation Digital presentation Reports Batches (current) Batches (completed) Counters and integrators Comment entry The comment entry does not have its own header. The current header will remain when this function is activated. The comment that has been entered is placed in the event list.
4 Visualization 4.3 Curve Presentation In this presentation, the individual signal traces run from top to bottom of the display (vertical presentation). Group step-on Channel step-on Numerical measurement display (diagram view) Memory presentation Group selection Sampling rate and oper. mode: = Normal mode = Event mode = Timed mode An alarm (Alarm 1 or Alarm 2) is indicated by a red or orange curve color. The colors can be configured in the setup program.
4 Visualization Channel step-on This function activates the scaling display. Repeated activation steps through the scaling for the channels within the group, and then blanks it out again. Programmable alarm limits Group step-on Unlike “Group selection”, where any group can be selected, this function is used to select the groups one after another. Group number 4.
4 Visualization 4.5 Text Picture Presentation In the presentation, the analog channels are presented numerically, together with the channel name and the channel description. In addition to the analog channels, the digital inputs can also be visualized at the right-hand edge of the display. Group presentation Channel name An alarm (Alarm 1 or Alarm 2) is indicated by an orange or red background. The colors can be configured in the setup program.
4 Visualization 4.6 Process Image Presentation The display shows selected measurement signals and background pictures in a maximum of nine process images. The setup program is used to prepare and configure the images. H 4.7 Each process image can be freely configured by the user. One background image (316 × 188 pixel) and 25 objects (analog/binary signals, icons, texts, bars) can be used per process image. Further information can be obtained from the instructions on the setup program (59492).
4 Visualization 4.8 Reports Each one of the reports covers all the analog channels in a group. Each group has its own configurable report. The current reports are visualized in the presentation. Group step-on Channel step-on Report step-on Group selection Maximum Minimum Average Time period Here you can find the completed report data for a Here you can find the completed report data for a channel.
4 Visualization 4.9 Batches/Plants When recording batch processes, a distinction is made between the plant and the batch. The instrument can combine and record the data from up to 3 plants in batches (batch report). The number of batches for a plant is not limited. The instrument distinguishes between “current batch” and the most recently “completed batch” for a plant. The number of plants that are used and the texts in the batch template can be configured on the instrument or in the setup program. 4.9.
4 Visualization Edit batch This function can be used to edit the batch text fields that are available (configured for this purpose). When the function has been called up, the first editable field in the screen template will be activated. h Press the control knob to start editing. h Enter the text (Chapter 26 "Entering text and values"). h Rotate the control knob to select a new field or button, and activate it by pressing the control knob.
4 Visualization 4.9.2 Completed Batches Change batch/plant Batch evaluation Batch evaluation Completed batches can be evaluated in three different ways: - Curves (graphical presentation) - Report (numerical presentation) - Attachments (e.g. recipes) h Rotate the control knob to select a type of presentation, then press the knob to activate this type. Activating the door symbol in the header closes the selected presentation, and the batch data will be displayed again.
4 Visualization 4.9.3 Batch Control with Barcode Reader If a barcode reader is connected to the interface “RS232 for barcode reader” (connector 2) or “RS232/RS485” (connector 7), then the batch start, batch stop, and input of batch texts in a current batch report, can be controlled by the barcode reader. The bar codes that are used all correspond to the type “Code39”. Preconditions - The interface must be configured for bar code operation.
4 Visualization Activate and display (if required) batch report for batch (plant) 3: Start and stop batch report If the batch report is configured for start/stop via barcode reader, then it will be started and stopped as follows. Start batch: h Scan bar code for “Batch report for batch (plant) 1 — 3”. h Scan start. Stop batch: h Scan bar code for “Batch report for batch (plant) 1 — 3”. h Scan stop.
4 Visualization Activate batch texts If a line in a batch report is configured for barcode activation, the activation proceeds as follows. Activate text: h Scan bar code for “Batch report for batch (plant) 1 — 3”. Scan text. The first line of the activated batch report that has been configured for text input via bar code will automatically be filled with the text that corresponds to the bar code.
4 Visualization 4.10 Counters and Integrators In this presentation, the current states of the counters and integrators (totalizers) are displayed, as well as the operating hours counter. Up to 9 counters and integrators can be shown in one screen template. The functional characteristics (counter, integrator or operating hours counter) are defined in the device configuration.
4 Visualization 4.11 Comment Entry This function can be used to enter a text (max. length 31 characters) that is entered in the event list when the input is completed. In curve presentation (in the displayed group), the text entry is marked by a pencil symbol. v Chapter 6 "Alarm and Event Lists" v Chapter 4.3 "Curve Presentation" v Chapter 4.11 "Comment Entry" The text can now be found in the event list, under the heading “All events”, but also under the corresponding batch.
4 Visualization 68
5 Memory Presentation (History) The Memory presentation function can be used to display and check data from the internal main memory (SRAM) of the instrument. The size of the memory for memory presentation can be configured. The memory presentation can be activated in the visualization modes “Curve presentation” and “Binary presentation”, and is also used to display completed batches.
5 Memory Presentation (History) Event list This function is used to present the event list for the group that is visible. The message that is closest to the cursor is shown in the list. v Chapter 6 "Alarm and Event Lists" Scroll lines Rotating the control knob moves the cursor through the visualization window. The data in the “Numerical measurement display” are updated every time there is a shift.
5 Memory Presentation (History) Search If you select “Search”, the dialog window for entering the date will be shown. h Select the date and time, and use OK to close the dialog. If the date that was entered is in the History memory, the cursor will move to this position and the data will be shown. Numerical measurement display This function decides whether the MAX or MIN values are shown in the “Numerical measurement display”. Min or Max values arise when more measurements are recorded than are displayed.
5 Memory Presentation (History) 72
6 Alarm and Event Lists The alarm and event lists can be called up in two ways: - A call from one of the visualization modes, e.g. curve presentation (diagram) (Chapter 4.2 "Overview of Header Lines") and - A call from the memory presentation (Chapter 5 "Memory Presentation (History)"). Alarm lists Alarm lists contain only the alarms and errors that are currently present. A Event lists The alarm list will not be updated as long as the window is open. Remedy: Close once, and open again.
6 Alarm and Event Lists 6.1 Call from One of the Visualization Modes h In the header line, rotate and press the control knob to select and activate the bell symbol. h Select the required list. Activate alarm list Complete list of alarms Batch-related alarm lists if the number of batches is reduced, then fewer entries will be displayed. h Rotate the control knob to select a list, then press the knob to activate the list.
6 Alarm and Event Lists h Rotate the control knob to select a list, then press the knob to activate the list. Example In the example, you can see a complete event list. Close list h Close the event list by pressing the control knob. The visualization that was active before the list was called up will now be displayed again.
6 Alarm and Event Lists 6.2 Call from the Memory Presentation h In the header line, rotate and press the the control knob to select and activate the bell symbol. Only the event list for the active group will be shown in the memory presentation. The message that is closest to the cursor is shown in the list. Close list h Close the event list by pressing the control knob. The memory presentation that was active before the list was called up will now be displayed again. 6.
7 Memory Manager The memory manager contains functions for data exchange between the paperless recorder and CF memory cards or USB memory sticks. Symbols The symbol for the Memory manager (menu: Memory manager) in the header can be shown in different ways. This shows the available memory of the CompactFlash memory card that has been inserted. Shows the available memory of the USB memory stick.
7 Memory Manager Activation for USB stick H Access to the Memory manager menu via the header is not possible with a USB memory stick. If one of the visualization modes (Chapter 4 - e.g. Curve Presentation) is active when a USB memory stick is inserted, the menu automatically appears and remains active until the memory stick is removed again. If not all functions are available, then you must log in to the device first, in order to obtain the required access rights. v Chapter 8.
7 Memory Manager H The functions of the memory manager are the same for CF cards and USB memory sticks. For USB sticks, the menu entries have "USB stick" instead of "CF card". Close memory manager (Exit) Close the memory manager and reactivate the previous visualization. Safely removing hardware The function should always be called before removing a CF card or a USB stick. This is the only way to ensure that files are properly stored on the data storage medium.
7 Memory Manager General information H H 80 The function CF card update reads out data that have not yet been read out. After read-out, data are not marked as read in the recorder but are not deleted. Function Backup CF card reads all data from internal memory, including what had already been read. After read-out, the data are marked as read in the recorder. The function Backup CF card is therefore ideal for test and service work.
8 Device Manager The functions of the Device manager vary, depending on whether a user is logged in or not. No user logged in “User” logged in User “Master” logged in Close Device Manager Log-in and log-out Device information Device audit trail Configuration Parameterization Service functions H The differences between “No user logged in” and “User logged in” only become visible in the submenu “Parameterization”.
8 Device Manager 8.1 Close Device Manager Close the device manager and reactivate the previous visualization. 8.2 Log-in and Log-out h Select the Device manager in the header, by rotating the control knob. h Activate the Device manager by pressing the control knob. h In the Device manager activate the function Log in. Log-in Log-out Change password Close dialog Default users Log-in H The paperless recorder is delivered ex-factory with an internal user list which contains two users. 1.
8 Device Manager h Select “OK” with the control knob, and press the control knob. h Enter the password by rotating and pressing the control knob, and finish the entry with “OK”. You are now logged in to the system.
8 Device Manager 8.3 Device information This function provides you with information on the hardware and software components of the instrument. The momentary values of all the internal and external inputs can also be checked. The control knob can be rotated to display every single table. The function is terminated by pressing the control knob.
8 Device Manager Info Module 1 = bottom module slot Module 2 = middle module slot Module 3 = top module slot Date and time of last reconfiguration Switching state of relay 1 (fitted as standard); 0= not switched Hardware Bottom module slot Middle module slot Top module slot RS232 for barcode reader 85
8 Device Manager Module 1 The picture below shows a module that has been fitted with 6 analog inputs. Depending on the hardware level, the picture may look different. Module 1 is in the bottom module slot. The * indicates that an offset or fine calibration is active on this channel. Module 2 Display of the current analog values from module The picture below shows a module that has been fitted with 3 analog inputs and 8 binary inputs/outputs.
8 Device Manager Module 3 The picture below shows a module that has been fitted with a relay card (6 relays). Depending on the hardware level, the picture may look different. Module 3 is in the top slot. Switching state of relays (0 = not switched). Ext. analog input (AE) 1 — 2 The two windows show the current external analog inputs. External analog inputs are read into the recorder via one of the interfaces (e.g. through the Modbus Master function). Ext.
8 Device Manager Eth. info 1 Information about the current Ethernet configuration Eth.
8 Device Manager Parameter Description Ethernet status 5 Received TCP packets Ethernet status 6 Received TCP packets with errors Ethernet status 7 Transmitted TCP packets Ethernet status 8 Transmitted TCP packets with errors Ethernet status 9 Received Lease time, in seconds USB info Information appears in the window via the USB interfaces. This information is only of interest for servicing. Interface Information about the serial interfaces and PROFIBUS DP interface appears in the window.
8 Device Manager 8.5 Configuration This function can be used to alter the configuration of the recorder. v Several chapters in this operating manual deal with the configuration, which starts in Chapter 10 "Configuration - General". A 8.6 An alteration of the configuration results in the current recording being closed down and the new data being recorded in a separate time frame from the “old” data.
8 Device Manager 8.7 Service The “Service” functions will also not be available if no user is logged in, or the user who is logged in does not possess access rights for these functions. Config. -> factory settings The current configuration can be saved within the device as the new factory setting. Restore factory settings The factory setting, e.g. created by “Set->curr. settings as default”, is called up and the instrument is reset.
8 Device Manager 92
9 Parameterization The functions in the Parameterization menu vary, depending on whether a user is logged in or not.
9 Parameterization 9.1 Fine calibration Using “Fine calibration”, an adjustment (correction) of the internal analog measurements can be activated. The adjustment is carried out using a linear equation. Example Systematic errors, such as those caused by an unsuitable probe mounting, have occurred in a plant. A probe provides measurements that cover a temperature range from 200 to 300°C.
9 Parameterization 9.4 Batches/plants Irrespective of the number of batches (plants) used, this function is available for configuring the start numbers of up to three batch numbers. The batch numbers can be switched into display when recording batches in the batch report. At the end of a batch, the value is incremented by one. Example: Batch numbers Current batch for Plant 1 Batch number 1 Batch numbers are assigned to a currently present batch in the menu Configuration Batches/plants.
9 Parameterization 96
10 Configuration - General The menu Device manager Configuration can only be called up if a user is logged in who is authorized to perform the configuration. H With the aid of the setup program, the user rights can be altered and transferred to the paperless recorder via the interface or CF card. Device Manager h Select the submenu by rotating the control knob. h Activate the submenu by pressing the control knob.
10 Configuration - General 98
11 Configuration - Device Data Overview Device (instrument) name The device name (up to 15 characters) is used for the identification of the paperless recorder in the instrument (Device info menu), in the setup program or in the PCA Communications software PCC. Language First choose between the two instrument languages. All texts (fixed and variable ones) can be altered through the setup program. Individual texts in any language can be implemented in this way.
11 Configuration - Device Data History (data) memory Here you can determine the size of the History memory. The memory is used to show stored measurement data that are outside the present curve view. The History presentation is started through the History function in the header. v Chapter 5 "Memory Presentation (History)" Data readout via ... The memory readout type of your choice is selected here. The parameter only affects the header, and when there is no CF card in the slot.
12 Configuration - Screen 12.1 Brightness … Show text image Overview Brightness With the aid of this function, the brightness of the screen can be altered in four stages (1 = darker; 4 = brighter). Any alteration to this parameter will become effective when the Instrument (device) data menu is closed. Switch off screen For screen saving, a screen switch-off (screen saver) can be activated here. The switch-off can be activated by means of a waiting time or a control signal.
12 Configuration - Screen Show curves (diagrams) This parameter determines whether curve presentation may be called up in the Visualization menu. Yes Show bar graph This parameter determines whether bar graph presentation may be called up in the Visualization menu. Yes Show text image Curve presentation can be called up. Bar graph presentation can be called up. This parameter determines whether textual presentation may be called up in the Visualization menu.
12 Configuration - Screen Show binary image This parameter determines whether binary screen presentation may be called up in the Visualization menu. Yes Binary screen presentation can be called up. In the presentation, the analog channels are dispensed with, only the binary channels are made visible. Show reports This parameter determines whether report presentation may be called up in the Visualization menu. Yes Report presentation can be called up.
12 Configuration - Screen 104
13 Configuration - Analog Inputs The analog inputs of the recorder are configured in this menu. How to connect the inputs to the recorder is described in the Installation Instructions 59488 (connectors 8 to 13, depending on the equipment level of the individual module slots). 13.1 Sensor … Offset Overview Sensor Type of the connected sensor (e.g. RTD in 3-wire circuit). The setting “Inactive” means that the channel is not connected.
13 Configuration - Analog Inputs If the limits can be altered, a free scaling function is activated within the instrument, i.e. the value “range start” is transformed to the value “scaling start” and the value “range end” to the value “scaling end”. If the limits are not alterable, the predefined range can only be restricted via “scaling start” and “scaling end”. Scale / range start / range end Visualization on the recorder screen takes place within the limits configured here.
13 Configuration - Analog Inputs Re Resistance between slider and start, if the slider is at the start. Rs Total resistance minus Ra and Re. The sum of the resistances (Ra+Re+Rs) must not exceed 4000 Ohm. Resistance R0 — Rp The resistance values can only be entered with the sensor type “potentiometer”. 1 2 3 4 R0 Resistance between slider and start, if the slider is at the start. Rp Total resistance minus R0. The sum of the resistances (R0+Rp) must not exceed 4000 Ohm.
13 Configuration - Analog Inputs 13.3 Comma format … Alarm Configuration Overview Comma format (decimal place) The decimal place serves to determine the number of integer and decimal places for the numerical presentation of the measurements. If required, the instrument will automatically switch to a different format, in order to be able to show all the integer places. As a rule: configuration all integer places must be displayed.
13 Configuration - Analog Inputs 13.4 Alarm configuration 13.4.1 Status … Alarm text 2 Overview (3) (3) alarm on alarm off (1) (2) (1) = Low alarm (2) = High alarm (3) = Hysteresis Status Status activates alarm monitoring. On Alarm type 1/ alarm type 2 Limit value 1/ limit value 2 Alarm monitoring is active. “Min alarm” and “Max alarm” are available for each alarm type. Min alarm Alarm is initiated if the value has fallen below the limit.
13 Configuration - Analog Inputs Hysteresis (differential) The hysteresis serves to prevent an unsteady (flickering) alarm state (repeated, brief switching on and off due to the noise of the input signal). The higher the value, the larger the amount by which the present measurement must go above or below the limit in order to cancel the alarm. Alarm delay This parameter delays the reporting of an alarm. If the alarm is no longer present after the alarm delay time has elapsed, it will not be triggered.
14 Configuration - Binary Inputs/Outputs The binary inputs and outputs of the recorder are configured in this menu. How to connect the inputs and outputs to the recorder is described in the Installation Instructions 59488 (connectors 9, 11 or 13, depending on the equipment level of the individual module slots). 14.1 Function … Alarm Configuration Overview Function This parameter determines whether a binary input or a binary output is to be used.
14 Configuration - Binary Inputs/Outputs Channel description Description of the input or output, up to 21 characters. The channel description is displayed in the individual visualization modes, together with the channel name. Alarm configuration Opens the submenu for the configuration of the alarm monitoring. 14.2 Alarm Configuration Overview Status Status activates alarm monitoring. On Alarm type Alarm monitoring is active.
14 Configuration - Binary Inputs/Outputs Alarm text Text that is entered in the event or alarm list and displayed in the “status & title bar”, with the alarm type “Alarm”. Alarm delay This parameter delays the reporting of an alarm. If the alarm is no longer present after the alarm delay time has elapsed, it will not be triggered. Alarm rejection This function makes it possible to suppress alarms when a binary signal is active (HIGH state). - Both alarm types (alarm and event) are suppressed.
14 Configuration - Binary Inputs/Outputs 114
15 Configuration - Relay The response of the relay(s) of the recorder are configured in this menu. How to connect the relay(s) is described in the Installation Instructions 59488 (connectors 1 and 14, depending on the equipment level of the individual module slots). Overview Binary signal Selection of the signal the chosen relay is to switch. Channel name (designation) Short designation for the relay, up to 7 characters.
15 Configuration - Relay 116
16 Configuration - External Analog Inputs The external analog inputs that are connected to the recorder are configured in this menu. The external inputs are connected via - one of the two serial interfaces (connector 2 or 7), - the PROFIBUS-DP interface (connector 3 - extra code), - the setup interface (connector 5) or - the Ethernet interface (connector 6). In the case of the two serial interfaces (connector 2 or 7), external inputs can be connected as a Modbus slave and as a Modbus master.
16 Configuration - External Analog Inputs Unit Unit in which the acquired measurement signal is to be displayed, up to 5 characters. The unit is displayed wherever the measurement is presented numerically. Comma format The decimal place serves to determine the number of integer and decimal places for the numerical presentation of the measurements. If required, the instrument will automatically switch to a different format, in order to be able to show all the integer places.
16 Configuration - External Analog Inputs Status Status activates alarm monitoring. On Alarm type 1/ alarm type 2 Alarm monitoring is active. “Min alarm” and “Max alarm” are available for each alarm type. Min alarm Alarm is initiated if the value has fallen below the limit. Max alarm Alarm is initiated if the value has gone above the limit. Limit value 1/ limit value 2 Limit at which the alarm is initiated.
16 Configuration - External Analog Inputs 16.2.2 Alarm rejection Overview Alarm rejection This function makes it possible to suppress alarms when a binary signal is active (HIGH state). - Both alarms are suppressed. - There is no indication of overrange, underrange or probe break. - Alarms that are present become inactive. - Overrange und underrange alarms become inactive. - There is no alarm or event entry when alarm rejection is active.
17 Configuration - External Binary Inputs The external binary inputs that are connected to the recorder are configured in this menu. The external inputs are connected via - one of the two serial interfaces (connector 2 or 7), - the PROFIBUS-DP interface (connector 3 - extra code), - the setup interface (connector 5) or - the Ethernet interface (connector 6). In the case of the two serial interfaces (connector 2 or 7), external inputs can be connected as a Modbus slave and as a Modbus master.
17 Configuration - External Binary Inputs 17.2 Alarm Configuration Overview Status Status activates alarm monitoring. On Alarm type Alarm monitoring is active. The alarm type determines whether the activating/inactivating of an input is to be evaluated as a genuine alarm or only as an event. Event The alarm text is entered in the event list only. Alarm The alarm text is entered in the alarm list and the event list.
17 Configuration - External Binary Inputs Alarm rejection This function makes it possible to suppress alarms when a binary signal is active (HIGH state). - Both alarm types (alarm and event) are suppressed. - Alarms that are present become inactive. - There is no alarm or event entry when alarm rejection is active.
17 Configuration - External Binary Inputs 124
18 Configuration - Groups In the Groups menu you can determine which channels (analog or binary, math, internal or external, counters and integrators) are to be displayed and/or recorded. Furthermore, you can decide here how data are to be recorded (storage cycle, storage procedure, economy operation). If batches are used, then these have a fixed assignments to the groups.
18 Configuration - Groups 18.1 Parameter Overview Status Name 126 This parameter determines what happens to the group. Inactive The data for the group will neither be displayed nor stored. This setting is only available from Group 2 on. If Group 4 or 7 is inactive, then the batch cannot be recorded for Plant 2 or 3. Display only The data for the group are displayed on the screen. Display and save The data for the group are displayed on the screen and stored.
18 Configuration - Groups 18.2 Analog Channels Overview Channel 1 Input signal The input (or input signal) selected here will be used as channel no. 1 for the group. All internal or external analog channels, as well as math channels (available as an extra), can be chosen. Channel 1 has been assigned a special task: it is used as a reference curve for the other channels of the group. All the other channels of the group can be compared with Channel 1, independently of each other.
18 Configuration - Groups Channel 1 plus the positive tolerance and minus the positive hysteresis for the alarm to be canceled again. The value for the “positive hysteresis” can only be entered as a positive value. Negative hysteresis If a negative tolerance infringement has occurred, the present measurement from Channel 2 — 6 first has to rise above the measurement from Channel 1 plus the negative tolerance and plus the negative hysteresis for the alarm to be canceled again.
18 Configuration - Groups Overview Channel 2 — Channel 6 Input signal The input (or input signal) selected here will be used as channel no. 2 — 6 for the group. All internal or external analog channels, as well as math channels (available as an extra), can be chosen. Line width Determines the width of the graphical measurement display. Thin/thick Thick Tolerance band active Thin If this function is active, the channel is compared with Channel 1 of the group. Yes Tolerance band comparison is active.
18 Configuration - Groups 18.3 Binary Channels Overview Input signal The binary input/output or signal is selected here that will be used for visualization. Max. 6 binary channels can be visualized and recorded in a group. 18.4 Counters/Integrators Overview Counters/ integrators (totalizers) Up to 4 out of a total of 27 available counters/integrators can be assigned to the group.
18 Configuration - Groups 18.5 Diagram View Overview H It is also possible to alter some parameters in the visualization Curves or Binary using the configuration. symbol, without having to alter the Diagram header is switched on. Binary channels are hidden. Perforation/punched edges is switched on. Perforation If perforation is switched on, then the perforated margin – familiar from chart recorders – appears in the curve display, on the left-hand and right-hand edges of the screen.
18 Configuration - Groups Diagram header With the help of this parameter, the diagram header can be switched on or off. The diagram header (numerical presentation of the measurements or switch symbols for the binary channels) is available in the visualization mode Curves and Binary. Measurement selection The parameter Measurement selection enables you to choose between MIN and MAX.
18 Configuration - Groups 18.6 Normal Operation Overview Memory status Only if Memory status is switched on, is the operating mode “Normal operation” available. With activated normal operation, the measurement data will be recorded at the storage cycle that was configured, unless - event operation is active, - timed operation is active or - the parameter Stored values is configured for Eco mode.
18 Configuration - Groups Eco Mode Using this method, the value is stored if the measurement differs by a certain amount from the value that was last stored, or if a binary channel belonging to the group alters its state. In Eco mode, the configured storage cycle is regarded as the maximum storage rate. In no case will values be stored any faster, even if they change faster.
18 Configuration - Groups 18.7 Event Mode Overview Binary signal Select which signal should start or terminate event operation. Stored values (memory values) v Chapter 18.6 "Normal Operation" - Page 133 Storage cycle (memory rate) v Chapter 18.6 "Normal Operation" - Page 134 Eco mode The parameters for Eco mode are set in the menu Normal operation.
18 Configuration - Groups 18.8 Timed Mode Overview Start Start time for initiating timed operation. If start = end, then timed operation is not active. End Stop time for terminating timed operation. If start = end, then timed operation is not active. Stored values (memory values) v Chapter 18.6 "Normal Operation" - Page 133 Storage cycle (memory rate) v Chapter 18.6 "Normal Operation" - Page 134 Eco mode The parameters for Eco mode are set in the menu Normal operation.
19 Configuration Report A report can be generated for each of the 9 groups . You can store the MAX/ MIN or average value for each analog channel in a report. H H H Procedure if the configuration is altered All reports are concluded, saved and restarted. The values of the concluded reports are set to “----” in the instrument. In this case, the result of the concluded reports can only be made visible through the PCA3000 software.
19 Configuration Report Total Total determines whether a report is run over the entire duration of the current recorder configuration. On Daily Daily determines whether a report is run over one day (24 hours). Conclusion and restart are determined by the parameter Synchronization time. On Weekly The total report is run. The daily report is run. Weekly determines whether a report is run over one week. Conclusion and restart are determined by the parameter Weekday and Synchronization time.
19 Configuration Report 19.2 External … Out of range Overview External External determines whether an external report is run while the external signal (External start) is set (HIGH). On H External start The external report is run. Only one external report will be started in a group within 5 seconds, i. e. any external restart before the 5 seconds have elapsed will be ignored. If the start signal is still present after 5 seconds, the external report will be started at once.
19 Configuration Report Synchronization time Synchronization time is used for the daily, weekly and periodic report, for the report end and restart. The parameter Synchronization time is explained below, using a period report as an example. Stop and restart will occur at the next instant of time which fits into the time grid, dependent on the Synchronization time and Period. Example: Period = 2 hours Synchronization time = 11:30:00 Power ON = 09:11:00 1. Period 1 from 09:11 to 09:30 = 19 minutes 2.
20 Configuration - Limit Monitoring Nine limit values are available for limit monitoring, in addition to the alarms at channel level. For a description of the alarms at channel level, see Chapter 13.4 "Alarm configuration". 20.1 Function … Alarm Configuration Overview (3) (3) alarm on alarm off (1) (2) (1) = Low alarm (limit value) (2) = High alarm (limit value) (3) = Hysteresis Function Analog value “Low alarm” and “High alarm” are available for each limit value.
20 Configuration - Limit Monitoring Limit value Limit at which the binary signal is activated. Hysteresis (differential) The hysteresis serves to prevent an unsteady (flickering) binary signal (repeated, brief switching on or off due to the noise of the input signal. The higher the value, the larger the amount by which the present measurement must go above or below the limit in order to cancel the alarm. Switch-on delay This parameter delays the setting of the binary signal.
20 Configuration - Limit Monitoring 20.2 Alarm Configuration Overview Status Alarm type Status activates alarm monitoring. Off Alarm monitoring is not active. On Alarm monitoring is active. In the event of an alarm, the binary signal “Alarm Limit 1 — 9” is set in addition to the binary signal “Limit monitoring 1 — 9”. The alarm type determines whether the activating/inactivating of a binary signal is to be evaluated as a genuine alarm or only as an event.
20 Configuration - Limit Monitoring Alarm delay This parameter delays the reporting of an alarm. If the alarm is no longer present after the alarm delay time has elapsed, it will not be triggered. Alarm text Text that is entered in the event or alarm list and displayed in the “status & title bar”, with the alarm type “Alarm”. Alarm rejection This function makes it possible to suppress alarms when a binary signal is active (HIGH state). - Both alarm types (alarm and event) are suppressed.
21 Configuration - Counters/Integrators Each of the 27 channels can be configured as a counter, integrator, operating time counter, high-speed counter, or for measuring flow rates in combination with high-speed counters. - Counters (counting frequency 8Hz) are used to count binary signals. - Integrators are used to integrate analog inputs. - Operating time counters are used to measure the time in which binary signals are active.
21 Configuration - Counters/Integrators Stop and restart will occur at the next point in time which fits into the time grid, dependent on the Synchronization time (Synch. time) and Period. Example: Period = 2 hours Synchronization time = 11:30:00 Power ON = 09:11:00 1. Period 1 from 09:11 to 09:30 = 19 minutes 2. Period 3 from 09:30 to 11:30 = 2 hours 3. Period from 11:30 to 13:30 = 2 hours etc.
21 Configuration - Counters/Integrators 21.2 Function … Specific Setting Overview Function Save Function determines whether the channel that was selected will be used as a counter integrator, operating time counter, high-speed counter, or for flow rate measurements. Counter The binary signal will be counted. Integrator The analog signal will be integrated. Operating time The operating time will be acquired using a previously set binary signal.
21 Configuration - Counters/Integrators Type Type determines when the current count is stored. According to the setting, the parameters from Chapter 21.1 "General Setting" must also be taken into account. Type Description Periodic Conclusion and restart are determined by the parameters Period and Synch. time. External Conclusion and restart are determined by an ext. control signal. The counters/integrators operate when the external signal is set (HIGH).
21 Configuration - Counters/Integrators 21.3 Input Signal … Decimal Place Overview Input signal Input signal which will be counted or integrated. If High-speed counter or Flow rate quantity was selected for the Function setting, Input signal is not available. The assignment cannot be changed. Weighting (evaluation) For binary signals (counter), each time the signal is set, the result is increased by the Weighting factor.
21 Configuration - Counters/Integrators With the function Flow rate quantity, the time base determines the counting duration of pulses (gate time) and display interval. Second The flow rate quantity is determined over the course of a second and displayed. Minute The flow rate quantity is determined over the course of a minute and displayed. Hour The flow rate quantity is determined over the course of a hour and displayed.
21 Configuration - Counters/Integrators 21.4 Range Start … Alarm Configuration Overview Range start and range end Range start and range end determine the lower and upper limit of the bar graph display. Range end Progress in % Range start H Alarm configuration Counters/integrators are represented with a maximum of 9 digits. At overflow that restart at 0.0. Opens the submenu for the configuration of both alarms.
21 Configuration - Counters/Integrators 21.5 Alarm Configuration Overview (3) (3) alarm on alarm off (1) (2) (1) = Low alarm (limit value 1) (2) = High alarm (limit value 2) (3) = Hysteresis Status Alarm type 1/ alarm type 2 Status activates alarm monitoring. Off Alarm monitoring is not active. On Alarm monitoring is active. “Low alarm” and “High alarm” are available for each alarm type. Low alarm Alarm is initiated if the value has fallen below the limit.
21 Configuration - Counters/Integrators Alarm rejection This function makes it possible to suppress alarms when a binary signal is active (HIGH state). - Both alarm types (alarm and event) are suppressed. - Alarms that are present become inactive. - There is no alarm or event entry when alarm rejection is active.
21 Configuration - Counters/Integrators 154
22 Configuration - Interface The interfaces are used by the paperless recorder to communicate with other systems (e. g. a PC that is running the setup program or the PCA communications software). H A detailed description of the entire range of interface functions and protocols can be found in the separate interface description 59494. Overview The interfaces for Ethernet (connector 6) and RS232/RS485 (connector 7) and the “RS232 for barcode reader” (connector 2) are provided as standard in the recorder.
22 Configuration - Interface 22.1 Ethernet The Ethernet interface can be used to connect the paperless recorder to a network. Communication is designed for 10Mbit/sec and 100Mbit/sec, and the network connection is made through an RJ45 socket. Overview A All settings that affect the Ethernet must be cleared with the responsible network administrator. A maximum of four users are permitted access to a paperless recorder simultaneously.
22 Configuration - Interface H An assigned address can be altered by the DHCP server. If, for example, the PCA communication software is used for the automatic collection of data, then the address must be altered within the software. The automatically assigned IP address can be read in the menu Device manager Device info Eth. Info (Chapter 8.3 "Device information"). IP address If automatic IP address assignment is not used (DHCP = OFF), then the IP address for the paperless recorder is set here.
22 Configuration - Interface 22.2 RS232/RS485 22.2.1 General Overview H In order for communication to take place – e. g. with the setup program – the interface parameters for the PC and the recorder must be identical at both ends of the connection. Device address For the RS485 type of interface, the device address for the paperless recorder must only occur once within a group of connected instruments on the same bus.
22 Configuration - Interface Data format Min. response time The data format that is to be used for operating the interface. 8 - 1 - no parity 8 data bits, 1 stop bit, no parity 8 - 1 - odd parity 8 data bits, 1 stop bit, odd parity 8 - 1 - even parity 8 data bits, 1 stop bit, even parity The minimum response time is the minimum time that the recorder will take before it sends a response to a data request.
22 Configuration - Interface Number of measurements The number of measurements to be read. The number “1” means that one measurement is made at every cyclical interval. If a number larger than 1 is entered, then (commencing at the Modbus address) several measurements will be read and automatically distributed to the following external inputs (analog values). The entry template will be locked for subsequent values. Example: starting at "Ext. analog value1“, three measurement values are read.
22 Configuration - Interface Addr. ext. text A maximum of 9 texts can be read into the paperless recorder. Device address The address of the slave device from which data are to be fetched. Modbus address Address within the instrument. v See the instrument documentation for the slave device. Word number The read-in is always made as words, i. e. there will always be at least two characters read. 22.3 RS232 for Barcode Reader Overview The settings correspond to those for the interface „RS232/RS485“.
22 Configuration - Interface 162
23 Configuration – Batches/Plants H H Please note the relationship between group and plant (batch). v Chapter 3.3 "Group and Plant Management (Batches)" v The visualization of batches (in progress and completed) is described in Chapter 4.9 "Batches/Plants". 23.1 General Information on Batches Batch reporting enables the creation of a flexible form to describe a batch process within the paperless recorder. A maximum of three batches (for 3 plants) can be recorded at the same time.
23 Configuration – Batches/Plants Batch texts How can something be edited? Texts can be edited on the device and with the setup software. They can also be sent to a device “online” with the setup software. Device: - Configuration - Batches/plants - Plant 1…3 - Line 1..10 - Content of right column and factory setting 1 Device - Visualization - Current batch - Select batch Texts can be edited on the device and with the setup software. Device: - Configuration - Batches/plants - Gen.
23 Configuration – Batches/Plants 23.2 General Plant Parameters Overview Number of plants Comment The parameter defines the number of plants for which a batch report will be created. 0 Batch reporting is not active. 1…3 A batch report is created for each active plant. For concluded batches, the text that is entered is shown as a header for a text of maximum length 400 characters, which is used to describe the batches (recipe or similar).
23 Configuration – Batches/Plants 23.3 Plant 1 — 3 Overview For each plant/batch, in addition to the “general plant parameters”, there are also some “general parameters” and the management of the contents in the right-hand column of the batch reports. 23.3.1 General Overview Plant name The plant name (maximum length 15 characters) is displayed in the status and title bar for the display of a current or concluded batch report, and can be used as a batch text in the right-hand column of a batch report.
23 Configuration – Batches/Plants Batch start Control signal This parameter defines how the batch report for a plant will be started and stopped. Inactive Batch reporting cannot be started. Control knob Batch reporting can be started and stopped by the operator, using the control knob on the instrument. Binary signal Batch reporting is started and stopped by one of the binary signals. Bar code Batch reporting is started and stopped by a barcode reader.
23 Configuration – Batches/Plants 23.3.2 Lines 1—10 Overview Right column contents This determines how the text is formed in the right-hand column of a batch report. Empty The field remains empty. Fixed text A fixed text is used, defined by the factory default parameter. Text list One of 128 device-internal batch texts is used. After a reconfiguration, the factory default text will be shown at first. The user has to select the required text from the list in the “Current batch” visualization.
23 Configuration – Batches/Plants Bin. combined text One of 128 device-internal batch texts is used. The selection is made through up to 6 binary signals. Chapter 23.3.1 "General" If, for instance, 2 binary signals are active, then 4 texts can be inserted. If all 6 binary signals are active, then 64 different texts can be inserted. Binary linkage 1 has the value 20, binary linkage 2 has the value 21, and so on.
23 Configuration – Batches/Plants Bar code The text in the selected line will be loaded by a barcode reader. v Chapter 4.9.3 External text 1 — 9 The text in the selected line will be loaded with one out of a maximum of nine interface texts. From Text No. This parameter is available if the text in the right-hand column is created from the internal text list, and is the first text from the list that is available for selection by the user. To Text No.
23 Configuration – Batches/Plants 23.4 Final Remarks The table below provides information again on the tools for configuring individual text fields. Text field Setup program (file) Text editor Texts in the left column yes yes Fixed text, text list, log. combined text, plant name, barcode texts, ext. text yes yes yes Additional text only yes Batch No.
23 Configuration – Batches/Plants 172
24 Configuration - Date and Time 24.1 Time Synch. … Daylight Saving Time Overview Time synch. This parameter can be used to influence the time setting for the paperless recorder. When used in conjunction with a binary signal it can thus ensure that several recorders are synchronized to the same time. Inactive No synchronization takes place. Binary I/O Select the signal that is to be used to activate the synchronization. The time is synchronized with the transition from Low to High (min.
24 Configuration - Date and Time Time zone (GMT) Daylight saving time 174 The GMT parameter (Greenwich Mean Time) defines the time zone (ignoring any daylight saving time shift) in which the recorder is being operated. This setting is important for evaluating data with the PC Evaluation Software PCA3000. Germany, France ... 1 h = 60 min England 0 Ukraine 2 h = 120 min Russia (Moscow) 3 h = 180 min This parameter determines whether the daylight saving time change is active or inactive.
24 Configuration - Date and Time 24.2 Start Daylight Saving When daylight saving time starts, the time is brought forwards by one hour. Overview Month The month in which daylight saving time starts is selected here. Day in current month This parameter is only available if a weekday has been configured in the “Day” parameter. In conjunction with “Day”, this sets which weekday in that month starts daylight saving time.
24 Configuration - Date and Time 24.3 End Daylight Saving When daylight saving time ends, the time is put back one hour. Overview Month The month in which daylight saving time ends is selected here. Day in current month This parameter is only available if a weekday has been configured in the “Day” parameter. In conjunction with “Day”, this sets which weekday in that month ends the daylight saving time.
25 Configuration - Undocumented Parameters Overview Undocumented parameters are used for extending the functionality of the paperless recorder. They should only be altered on express instruction from the manufacturer.
25 Configuration - Undocumented Parameters 178
26 Entering text and values 26.1 Text entry 26.1.1 Entering characters If a Text entry field is selected, and then activated by pressing the control knob, then a text can be entered or altered. The cursor (position marker) is at the end of the current setting. The active key or function that will be performed when the control knob is pressed is shown in blue. Cursor Insert spaces. Select text from a list. Available characters Shift cursor position within entry template.
26 Entering text and values Character entry h Move the cursor onto the required character, and press the control knob. Another selection window will open. Reject entry Upper case letter Lower case letter h Rotate the control knob to select upper case (capital) or lower case (small) letters, or reject an entry, and activate/confirm the choice by pressing the control knob. Entering special characters Special characters are entered as text. h Select the # symbol and press the control knob.
26 Entering text and values Select temperature unit h Select “ ” and press the control knob. All the temperature units that can be selected will now be shown. For better legibility, the degree sign (°) and the unit of measure (C or F) are separated, and must be individually selected. The selection and confirmation of the symbol is made by rotating and pressing the control knob. 26.1.2 Insert spaces h Select the space button ( ) and press the control knob.
26 Entering text and values 26.1.7 Reject entry h Select the “Cancel” button ( ) and press the control knob. Character entry will now be ended. The text that was entered is not accepted, and the dialog window is closed. The previously active setting is retained. 26.2 Entry via selection field If a selection field is selected, and then activated by pressing the control knob, then the text (value) can be entered from a previously defined list. The cursor (position marker) is on the current setting.
26 Entering text and values 26.3 Entering values 26.3.1 Whole numbers (integers) There are two possibilities for entering integer numbers: - selection by altering the individual digits of a number, or - selection by incrementing and decrementing. Digit-by-digit entry of an integer For this entry, each digit of the number (units, tens, ...) and the sign are selected with the control knob. Example h Select “2” (the tens digit) by rotating the control knob ( ). h Press the control knob.
26 Entering text and values 26.3.2 Real numbers (floating point) To enter real numbers (with a decimal point), each digit of the number (units, tens, etc.), the decimal point position, and the sign are selected with the control knob. Sequence - Position the cursor. - Enter the number or define the decimal point position. For number entry, the number is inserted at the right of the cursor. Cursor positioning h Select “Cursor” and press the control knob. The real number is indicated by a blue background.
27 Web server 27.1 General The web server is integrated in the paperless recorder as a standard feature. Four different modes of presentation are available: - „Online Visualization (All Visualizations Except Batches)“ - „Three freely programmable HTML pages“ - „Online Visualization of Current Batch Reports“ - „4-Way View“ The web server can be accessed on the PC side with Microsoft® Internet Explorer by entering the IP address (e. g. http://10.10.90.45). DNS names can be assigned on the device.
27 Web server Home page Online visualization automatically comes up as the home page if the web server is started by the browser or, if it has already been activated, the user (left) clicks the "Recorder" link.
27 Web server Navigation Configurable device name; read automatically Online visualization v Chapter 27.2 Three freely programmable HTML pages; created with the setup program v Chapter 27.3 Online visualization of current batch reports v Chapter 27.4 Start of 4-way view (quad view) Configuration of 4-way view v Chapter 27.5 Individual pages can be brought up by clicking (left mouse button). Visualization area The visualization area shows current data for the paperless recorder.
27 Web server 27.2 Online Visualization (All Visualizations Except Batches) Data that are displayed correspond to the configured groups of the recorder. Next group Next channel History Groups Visualization Alarm/event list The sample screen shows the web server's home page. This page can be used to represent channels in the same manner as on the recorder's screen. (Left) click to bring up the available menus of the recorder.
27 Web server Example Switching to bar graph presentation h (Left) click the Visualization menu. h (Left) click the bar graph. Result: The bar graph visualization type is activated.
27 Web server 27.3 Three freely programmable HTML pages The sample screen shows one of three freely programmable HTML pages. These pages can be created and modified with the setup program. H 190 Further information can be obtained from the instructions on the setup program (59492).
27 Web server 27.4 Online Visualization of Current Batch Reports When batch pages of a plant are called up, the current data from the recorder is read and displayed.
27 Web server 27.5 4-Way View Visualization for up to four devices is possible with 4-way view. The visualizations may involve one device or up to four different ones. Different visualizations can be activated for each display (for example two views of a device, curve presentation and bar graph display). Before 4-way view can be used, the function must be configured. h (Left) click "Setup". Setup The setup window appears, where all IP addresses in use can be configured.
27 Web server Result: IP addresses (or DNS names) that have been entered are saved as cookies in the PC and remain intact until cookies are deleted (forexample by the PC browser). h Click "Start" or "Start visualization". Result: 4-way view starts. In the example shown here, two different recorders are accessed (recorder 1 top left and top right, recorder 2 bottom left and bottom right). Two different visualizations are shown for each recorder.
27 Web server Unlike a normal online visualization, the header contains modified buttons.
28 Appendix 28.1 Bar code 28.1.
28 Appendix 28.1.
28 Appendix 345435 Job numbers A83737 A4555455 A455445 Personnel number 4576 7665 197
28 Appendix 198
29 Index Numerics 1-channel presentation 57 4-way view 192 A Active operating mode 35 Alarm and event lists 44, 73 Alarm delay 144 Alarm limits 56–57 Alarm lists 73 Alarms, analog inputs 32 Alarms, counters/integr. 32 Alarms, ext. Analog inputs 32 Alarms, ext.
29 Index Binary traces 132 C CF card -> config.
29 Index Diagram header 44, 58, 132 Diagram speed 34 Diagram view 46, 131 Digital presentation 103 Display 17, 19 Display off 18 Displays and controls 17 DNS 157, 185 E Eco mode 35, 133–136 Edit batch 61 Electrostatic discharge (ESD) 9 Entering values 183 Envelope 132 Eth. info 88 Ethernet 155–157 Event lists 73 Event Mode 135 Event mode 34, 55 Ext. binary input 31 Ext.
29 Index History 44, 69 History memory 100 Hysteresis (differential) 128, 142 I Info 85 Installation Instructions 15, 21–22 Instrument documentation in printed form 10 Instrument documentation in the form of PDF files 10 Integrator 23 Integrator with Out of Range 99 Integrators 23, 66, 130, 145 presetting 26, 94 reset 26, 94 Interfaces 155 Internal analog inputs 20–21 Internal memory 37 Introduction 9 IP address 157, 185 K Keys 13 L Language 99 Life-cycle data management 40 Limit alarms 31 Limit monitori
29 Index Memory managers 77 Memory presentation 44, 55, 69 MIN/MAX value recording 132 MIN/MAX values 132 Modbus 157, 159 Master 159 Module 86 N Nameplate 20, 22 Network 156 Normal display 48 Normal mode 55, 133 Normal operation 34 Note signs 12 Numerical measurement display 18, 44, 46, 55, 69 O Operating mode 55 Operating modes 34 Operating time counter 24, 145 reset 26 Operator level 44, 48, 53 Out-of-range 140 Over value 110, 117, 120 Overrange 106, 110, 117, 120 P Parameterization 90, 93 Password 82,
29 Index Report step-on 59 Reset (counter/integrator) 26 Returning 9 Rights 82, 97 RS232 161 RS232 / RS485 155, 158 RS232 for barcode reader 161 S Sampling rate 55 Save all + update CF card 79 Screen 101 Screen saver 18 Screen switch-off 101 Screen texts 13 Scroll 69 Search 69 Serial interface 20–21 Service 91 Setup program 97 Stainless steal 16 stainless steel 15 Status bar 18, 45 Status LED 17, 19 Storage cycle (memory rate) 34, 38, 134 Storage status 133 Stored value 34, 38, 133 Supply frequency 99 SVG
29 Index U Under value 106, 110, 117, 120 Underrange 106, 110, 117, 120 Undocumented parameters 177 Update CF card 79 USB 18, 39–40, 77–79 User 185 User list 79 Users 81–82, 93 logged in 81, 93 logged out 81, 93 Standard (default) password 82 Standard (default) user 82 V Value below measurement range 106, 110, 117, 120 Version 84 Visualization 44, 53 Visualization window 18, 47 W Warning signs 12 Warranty 9 Web server 185 Weighting (counter/integrator) 23–24 Writing configuration data to CF card / reading
29 Index 206
2009-08-07/00578758 Austria China France Germany UK USA T: +43 (0) 2236 691 121 T: +86 22 8398 8098 T: +33 (1) 77 80 90 40 T: +49 (0) 561 505 1307 T: +44 (0) 1273 606 271 T: +1 800 866 6659 Email Website Inquiries@West-CS.com www.West-CS.