10 Electrical connection
Terminal assignment
(for pluggable screw terminals)
3/6 channel paperless recorder
Diagram
Analog inputs Connector
Thermocouple 1 to 6
If sizeable supply interference is present on a thermocouple input, then the
corresponding analog input requires a link from terminal 2 to terminal 4.
Increased interference voltages can, for example, be generated by ceramic
insulation becoming conductive at temperatures of several hundred °C.
Resistance thermometers
in 2-wire circuit
1 to 6
Resistance thermometers
in 3-wire circuit
1 to 6
Resistance thermometers
in 4-wire circuit
1 to 6
Voltage input 210mV 1 to 6
Voltage input 210mV 1 to 6
Current input 1 to 6